Toshiba 18 - 1250 A Instruction Manual page 95

Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
Appendix 6 (cont.) Soft Starter Settings Record
Fn #
Group
Function Description
Pump Flex Control /
F024
Deceleration Ramp
Begin Decel Level (BDL),
F025
Immediate Drop Down Torque
F026
Decel Shut Off Voltage
F027
Decel Ramp Time
Restart Delay Time
F028
(Sequential Start Delay)
Reserved for Factory Use
F029
Process Control Timer
F030
Selection
Run Timer Time
F031
for use in F030 above
Time Clock Controller (TCC)
Start Event Mode.
Chose from "One Shot"
F032
or 1 to 7 "Start Events"
in F033 – F039
Run time for this mode comes
from F030 above.
F033
Start Event #1 Start Time
F034
Start Event #2 Start Time
F035
Start Event #3 Start Time
F036
Start Event #4 Start Time
F037
Start Event #5 Start Time
F038
Start Event #6 Start Time
F039
Start Event #7 Start Time
Adjustment / Display Range
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
1 – 60 Seconds
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
0 = Disabled (No timer operation)
1 = Minimum Batch Run Timer
2 = Permissive Run Timer
1-9999 minutes after a Start
Command or Start Event from TCC
Start Event Cycle (SEC) Settings
24hr
0 = One Shot: Start Event comes
from Start command only
1 = Loop SEC every day
2 = Loop SEC every 2
3 = Loop SEC every 3
4 = Loop SEC. every 4
5 = Loop SEC. every 5
6 = Loop SEC. every 6
7 = Loop SEC one day per week
8 = Single 24hr SEC
(until programmed again)
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
Digital Solid State Soft Starters 18 – 1250A
Setting
Increments
1
1%
1%
1 second
1 second
1
1
nd
day
rd
day
1
th
day
th
day
th
day
1
1
1
1
1
1
1
88
Factory
Setting
Setting
Setting
0
Disabled
60%
30%
10
seconds
0
Disabled
0
Disabled
1
0
One Shot
OFF
OFF
OFF
OFF
OFF
OFF
OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Te series