Toshiba 18 - 1250 A Instruction Manual page 38

Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
Fn #
Group
F019
F020
F021
Table 5.5.3: Jog Mode Function Group
Fn #
Group
F022
F023
Table 5.5.4: Kick Start Mode Function Group
Fn #
Group
F024
F025
F026
F027
Table 5.5.5: Pump Flex Decel Mode Function Group
Fn #
Group
F028
F029
Table 5.5.6: Restart Function Group
5.5.3
Function Description
Voltage Jog
Time of Voltage Jog
Current Jog
5.5.4
Function Description
Kick Start Voltage
Kick Start Time
5.5.5
Function Description
Pump Flex Control /
Deceleration Ramp
Begin Decel Level (BDL),
Immediate Drop Down Torque
Decel Shut Off Voltage
Decel Ramp Time
5.5.6
Function Description
Restart Delay Time
(Sequential Start Delay)
Reserved for Factory Use
Digital Solid State Soft Starters 18 – 1250A
Jog Mode Functions
Adjustment / Display Range
5 – 100% Line Voltage
1 – 20 Seconds
100 – 500% Motor Current
Kick Start Mode Functions
Adjustment / Display Range
0 = Disabled, or
10 - 100% Line Voltage
0.1 - 2 Seconds
Decel Mode Functions
Adjustment / Display Range
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
1 – 60 Seconds
Restart Function
Adjustment / Display Range
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
31
Setting
Factory
Section
Increments
Setting
1%
50%
10
1 second
seconds
4.2.5.b
1%
150%
Setting
Factory
Section
Increments
Setting
0
1%
Disabled
0.8
0.1second
seconds
Setting
Factory
Section
Increments
Setting
0
1
Disabled
1%
60%
Append.
1%
30%
10
1 second
seconds
Setting
Factory
Section
Increments
Setting
0
1 second
Disabled
5.6.3
and
5.6.4
5.6.5
and
2
5.6.6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Te series