An optically isolated Triac output is dedicated as a fault indicator on
PTC
OPTO
TB1, terminals 11 and 12, labeled "Opto". The output Triac switch is
rated for 10 - 250 VAC/DC, 50 mA (maximum). If the three
programmable Output Auxiliary Relays are being used for other
11
12
functions, this output can easily be hooked up to a PLC or small
external relay to provide a Fault signal. This Fault Output operation is
R
permanently fixed at "Any Trip", duplicating the Relay setting #16 as
External Fault Relay
shown in Table 5.6.10.
or PLC Input
This output is permanently set to this function and is not
programmable.
4.2.8
Three programmable auxiliary relays are on TB2. The TE Series starter
comes with three programmable dry relay output contacts. Outputs #1
and #2 are Form C (SPDT), with a Common, N.O. and N.C. Output #3
is a Form A, (SPST), N.O. contact. It is not necessary to use the
K5
programmable output auxiliary relays in the Start / Stop circuit. An
internal seal-in relay is provided elsewhere (see 4.2.2.a above). Toshiba
recommends fusing all contacts with external fuses.
The relays are rated for 240 VAC, 5 A and 1200 VA.
Factory default settings for these relays are as follows:
AUX 1 – Run / Stop (see F060) This contact changes state upon a
3
1
NO.
C
A1 A2
Start command, returns to normal on Stop (or Begin Decel if active).
AUX 2 – At-Speed / Stop (see F061) This contact changes state
19
20
upon the TE Series detecting At-Speed, and returns to normal on
Stop. At-Speed is determined by the TE Series detecting the
AUX.
RELAY #3
current dropping after reaching End-of-Ramp, or a maximum of 30
seconds after Start.
AUX 3 – Any Trip (see F062) This contact closes when any trip
condition # 5 – 15 (as defined in Table 5.6.10) occurs.
All relays can be reprogrammed for a wide variety of functions.
See Section 5.6.10 for additional relay programming details.