Table 5.6.13.a: Fault History Configuration
5.6.13
F085 – F097 contain the Fault History and Statistical data about the
Run Mode.
5.6.13.a
Fault codes for each of the three latest events are stored with time
and date stamps; see Chapter 7 for a complete list of fault codes
and corresponding error displays.
Time stamps use the 24hr HH.MM format, so for example 3:19 PM
would display as [15.19]
Date stamps use the MM.DD format, so for example September 3
would display [09.03]
Fault code:
Time Stamp
(HH.mm)
Date Stamp
(MM.DD)
F085 = Latest Fault Code (Fault #1)
F086 = Time Stamp of the Latest Fault
F087 = Date Stamp of the Latest Fault
F088 = Same as F085 except for the Previous Fault (Fault #2)
F089 = Same as F086 except for the Previous Fault.
F090 = Same as F087 except for the Previous Fault.
F091 = Same as F085 except for the Oldest Fault (Fault #3)
F092 = Same as F086 except for the Oldest Fault
F093 = Same as F087 except for the Oldest Fault
Digital Solid State Soft Starters 18 – 1250A

Fault History and Statistical Data

Fault History
Fault #1
(Latest Fault)
(Previous Fault)
F085
F086
F087
Factory Setting = 0 (No Fault)
Range = 0 – 27
This Function displays the Fault Code of the latest fault event.
Factory Setting = 00.00 (No Fault)
Range = 00.00 – 23.59 (24hr time format)
This Function displays the time of the latest fault event.
Factory Setting = 00.00 (No Fault)
Range = 01.01 – 12.31
This Function displays the date of the latest fault event.
60
Fault #2
Fault #3
(Oldest Fault)
F088
F089
F090
rd
F091
F092
F093