Toshiba 18 - 1250 A Instruction Manual page 68

Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
Digital Solid State Soft Starters 18 – 1250A
5.6.13.b
Statistical Data
F094 - F097 display information from the Run Time / Elapsed Time
meter and Run-Cycle counter.
Run Time includes Accel, Run, Decel, and Jog operations.
Run Cycles are counted only when the starter reaches At-Speed
mode.
F094 = Run Time, Hours
Factory Setting = 0000
Range = 000.9 - 999.9 hours
Run counts in excess of 999.9 are recorded in F095.
F095 = Run Time, K Hours
Factory Setting = 0000
Range = 0000 - 9999 K hours
0001 in readout means a run time of 1,000 hours.
F096 = Run Counts
Factory Setting = 0000
Range = 0000 – 9999
Run counts in excess of 9999 are recorded in F097.
F097 = Run Counts, 10K Times
Factory Setting = 0000
Range = 0000 - 9999, 10 thousand times
0001 in readout means a run count of 10,000 operations.
23,047 Hours
18,702 Starts
Table 5.5.15: Statistical Data Examples
61
Overflow
Examples:
Value
Run Time
Run Counts
Basic
Value
F095
F094
0002
3047
F097
F096
0001
8702