Example: Figure App 4.3
Time Clock Controller with Minimum Run Timer
An irrigation pump fed from a well with a single float level control
needs to come on every other day at 5:30 PM, and run for ½ hour.
If during that ½ hour the well level drops and shuts the pump
down, the pump needs to restart when the well recovers and finish
the ½ hour pump time.
Set F030 to [0001] for Minimum Run Timer.
This will ensure that when the well level recovers and resets the
run command, the starter will finish the time sequence.
Set F031 to [0030] (minutes)
This is the Batch Time that ensures the proper amount of irrigation
getting to the crop.
Set F032 to [0002] for Every 2
This will begin the Start Even Cycle on the day of programming
and every other day from then on.
Set F033 to [17.30]
This is the 24HR time value representing 5:30 PM. At this time,
every other day, the TE Series starter will automatically start
(provided the Stop float in the well is closed) and run for 30
minutes as programmed in F030.
If the pump needs to come on again at 7:00 PM, program F034 to
[19.00]. If later on it is needed to come on at 6:00 AM as well,
simply change any other unused start time, i.e. F038 to [06.00].
Even though this is Event #6 and the lower numbered events had
later start times in the program, the starter will execute #6 on time
in the next available cycle.
If the pump needs to come on every day, program F032 to [0001].
Digital Solid State Soft Starters 18 – 1250A
nd
Day
NOTE:
If programming is entered AFTER the set time value, the TCC will
wait until the next valid time before executing (i.e. if you entered the
above example program changes at 5:35 PM, the pump would not
come on automatically until 5:30 PM 2 days from now).
81
Example: Process Timer and TCC
for Irrigation Pump
Display
Shows...
F030
Press
Key...
READ
0000
ENTER
0001
READ
End
ENTER
F031
READ
0000
ENTER
0030
x 3
READ
End
ENTER
F032
READ
0000
ENTER
0002
x 2
READ
End
ENTER
F033
Set to 17.30
17. . 3 0
(5:30 PM military)
READ
End
ENTER
F033
Cycle Control Power to Accept Changes
Figure App 4.3: Programm ing Tim er Functions
M eans...
Starting at
Function #30
Default Setting
of Function #30
Set F030 = 1
M in. Batch Timer
Value Accepted
(flashes once)
Change to
F031
Default Setting
of Function #31
Change Setting
to 30 minutes
Value Accepted
(flashes once)
Change to
F032
Default Setting
of Function #32
Set to 2:
Every 2nd Day
Value Accepted
(flashes once)
Change to
F033
Value Accepted
(flashes once)
Return to
Function # Display