Toshiba 18 - 1250 A Instruction Manual page 33

Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
Example 1: Figure 5.4.3
Viewing a Function's Set Value
[0000.] Indicates Phase A is drawing no current
(unit is in Off mode).
Press the [Fn] key
[F001]
Indicates this is Function 001 (Motor FLA).
Press [READ/ENTER] key
to view the F001 value
[0048]
Indicates the programmed motor FLA is 48 Amps.
The farthest left digit (8) is flashing, indicating that
this is the digit that you will alter (cursor position).
Press the UP Arrow key
to increase this digit value
[0049]
Indicates you have increased the left digit to a
value of 9.
Press the LEFT Arrow key
to shift left to the next digit
[0049]
The second digit from the left is now flashing,
indicating a new cursor position.
Press the UP Arrow key
to increase this digit value
[0059]
Indicates you have increased the 2
a value of 5 (10's place).
Press [READ/ENTER] key
to store the new value
[End]
The word "End" will flash briefly to indicate that
the new value has been entered and accepted.
After flashing once, the display will revert to
showing the Function number.
Digital Solid State Soft Starters 18 – 1250A
5.4.2
Enabling Password Protection / Parameter Lock
The TE Series starter is shipped with the password protection disabled
(F070 = 0). If it becomes necessary to prevent parameters from being
changed inadvertently, set the password in function F070. See
Appendix 3 for details. If the display reads [ Loc] when the
[READ/ENTER] key is pressed, the parameter lock is enabled.
5.4.3
Changing a Function's Set Value
From the instructions above, after hitting the [READ/ENTER] key the
display will show the value of that function with one digit flashing
(usually the rightmost digit). Flashing indicates this is the digit to be
altered (similar to cursor position). Use the UP arrow key to increment
the value of the flashing digit. Use the DOWN arrow key to decrement
the value of the flashing digit. Use the LEFT or RIGHT arrow to select
the next digit to be altered. Values can only be changed within the
Adjustment Range of the function parameter.
nd
to left digit to
26
Example 1: Setting the Motor FLA
Change FLA from 48 to 59A
Display
Means...
Shows...
Phase A
0000.
Press
Current
Key...
Function #1
F001
Fn
Selected
Previous Setting
READ
0048
ENTER
of Function #1
New Value of
0049
First Digit
Cursor (flashing)
0049
Position Shift
New Value of
0059
Second Digit
Value Accepted
READ
End
ENTER
(flashes once)
Return to
F001
Function # Display
Figure 5.4.3:
Changing a Function Value