Toshiba 18 - 1250 A Instruction Manual page 48

Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
NOTE: Jog functions may become disabled by Comm port function F068 setting 3.
See section 5.6.11 for details.
CAUTION
Although the Thermal Register tracks all motor current use, continuous usage of the Jog
feature risks thermal motor damage or nuisance tripping.
Jog Voltage
Voltage Ramp
Setting
Jog
Command
M ax.
Jog
Time
Time
Figure 5.6.3.1:
Voltage Jog and Jog Time
Jog Current
Current Ramp
Setting
Jog
Command
New Start
Command
Time
Figure 5.6.3.2:
Current Jog
5.6.3
The Jog Function is another user optional feature and is controlled by
closing the input on TB1 Terminals 6 and 7. If this input is left open, the
TE Series will ignore all Jog settings. Engaging the Jog feature along
with the Start / Run Command provides an output from the SCRs, but
will not continue ramping to full acceleration. This feature can Jog the
motor at either a preset Voltage (F019 – F021) or a preset Current
(F021) depending upon the settings of the Ramp Type from F010, and
can be initiated along with Ramp 1 or Ramp 2 (see Dual Ramp Select,
Section 4.2.5 and 5.6.2.a). It is also sometimes useful to use Jog in
combination with Ramp 2, see section 4.2.5.c.
Setting
Ramp &
from
F010
1
Voltage
2
Current
3
Voltage
4
Current
Table 5.6.3: Jog Settings
F019 = Voltage Jog
New Start
Command
F020 = Time of Voltage Jog
F021 = Current Jog
Digital Solid State Soft Starters 18 – 1250A
Jog Mode
Ramp 1 (Dual Ramp Input
Open)
Initial
Jog
Torque
Torque
Type
from...
from...
F011
F019
F012
F021
F011
F019
F012
F021
Factory Setting = 50%
Range = 5 - 100%
Sets the voltage level of the Jog feature and is typically used to
check rotation, alignment, or to slowly move a load into position.
Jogging at a set voltage has no current control so the duration
of the applied voltage must be limited to prevent excessive
motor heating.
Factory Setting = 10 seconds
Range = 1 - 20 seconds
Set to minimize motor heating during a voltage jog. This setting
is the maximum allowable time for jogging the motor using
voltage only.
Factory Setting = 150%
Range = 100 - 500%
Sets output of a current Jog. The current jog feature is typically
41
Ramp 2 (Dual Ramp Input
Closed)
Jog
Ramp &
Initial
Jog
Torque
Type
from...
Voltage
F015
Current
F016
Current
F016
Voltage
F015
Jog
Torque
from...
F019
F021
F021
F019