TE Series
Example: Figure App 3
Enabling Password Protection / Parameter Lock
Starting from the Status Display Mode, no previous function
number entered, no existing password...
Press the Fn key.
Displays F001 to indicate the beginning of the function list.
Press the LEFT arrow key
Selects the second digit (from the right). NOTE: do it in this
order because F000 would not have been a valid number
Press the UP arrow key seven times (7X)
Changes the function code to F071.
Press the RIGHT arrow key
Selects the first digit (from the right).
Press the DOWN arrow key
Changes the function code to F070.
Press the Read Enter key
The default display will show [3552] as long as no password
has been previously entered. This is the default code for
"0000", meaning that there is no password. As soon as you
press the first Arrow key, the display will change to [0000]
and begin showing the actual value of your password entry.
Any initial display other than [3552] signifies that a password
already exists. This means that you will need to change, rather
than enter a new one (see below).
Use the UP arrow and the LEFT arrow keys...
to display the password you desire (Valid range is 0000 to
0999). In this example, 0123 has been selected.
Press the Read Enter key
The display will flash [End] to confirm you have entered a
password. Then it will return to displaying thee Function #.
Digital Solid State Soft Starters 18 – 1250A
Changing passwords:
To change an existing password, the steps are essentially the same as
outlined above, except you must first enter the existing password. At
F070, press the [READ/ENTER] key to reveal the encoded password
(you must know that password before it can be changed). Use the
Arrow keys to enter the password. As soon as you press the first Arrow
key, the display will change to [0000] and start showing the actual value
of your entry. When you get to the existing password, press the
[READ/ENTER] key again. The display will flash [PASS] to indicate that
the password was accepted. If it flashes [ Err ], you have entered the
wrong password.
Resetting to Factory Defaults using F071 will NOT reset the password.
Disabling Password Protection / Parameter Lockout
Changing function F070 to [0000] will disable the user password. If the
initial display reads [3552], the password is already set to [0000].
73
Example: Setting a Password
Using Password 123
Display
Means...
Shows...
Phase A
0000.
Press
Current
Key...
Select
F070
Fn
Function #70
Default Setting
READ
3552
ENTER
of Function #70
0003
x 3
Cursor (flashing)
0003
Position Shift
New Value of
0023
x 2
Second Digit
Cursor (flashing)
0023
Position Shift
New Value of
0123
Second Digit
READ
End
ENTER
F070
Figure App 3:
Entering a Passw ord
New Value of
First Digit
Value Accepted
(flashes once)
Return to
Function # Display
2