Brocade Communications Systems DCX-4S Backbone Hardware Installation Manual page 49

Hide thumbs Also See for DCX-4S Backbone:
Table of Contents

Advertisement

1. Power LED
2. Status LED
3. CEE port 9
4. Status LED for CEE port 9
5. CEE port 19
6. Status LED for CEE port 19
The following table describes the port, application, and encryption blade LED patterns and the
recommended actions for those patterns.
TABLE 5
LED purpose
Power LED
Status LED
FC Port Status
Brocade DCX-4S Backbone Hardware Installation Guide
53-1001191-15
Port, application, and encryption blade LED descriptions
Color
Steady green
No light (LED is off)
No light (LED is off)
Steady amber
Slow-flashing amber (on 2
seconds, then off 2
seconds)
Fast-flashing amber (on
1/2 second, then off 1/2
second)
No light (LED is off)
Monitoring System Components
Status
Recommended action
Blade is enabled.
No action required.
Blade is not powered on.
Ensure that the blade is
firmly seated and either
the thumbscrew is fully
engaged or the slider is
pushed up and the
ejectors are fully engaged.
Blade is either healthy or
Verify that the power LED
does not have power.
is on.
Blade is faulty.
Ensure that the blade is
firmly seated and check
the status by entering the
slotShow command.
Blade may not be
compatible with other
blades in the chassis. See
FCOE10-24 blade
page 111 for limitations. If
LED remains amber,
consult the Brocade
DCX-4S supplier.
Blade is not seated
Pull the blade out and
correctly or is faulty.
reseat it. If LED continues
to flash, replace the blade.
Environmental range
Check for out-of-bounds
exceeded.
environmental condition
and correct it.
Port has no incoming
Verify that the power LED
power, or there is no light
is on, check the
or signal carrier detected.
transceiver and cable.
Polling is in progress.
Allow 60 seconds for
polling to complete.
Connected device is
Verify the status of the
configured in an offline
connected device.
state.