Rohs; Other Approvals; Emc And Environmental Type Tests - Siemens SIMATIC NET RUGGEDCOM RS400F Installation Manual

Rugged
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS400F:
Table of Contents

Advertisement

6.1.6

RoHS

This device is declared by Siemens AG to meet the requirements of the following Ro-
HS (Restriction of Hazardous Substances) directives for the restricted use of certain
hazardous substances in electrical and electronic equipment:
A copy of the Material Declaration is available online at
try.siemens.com/cs/ww/en/view/109738831.
6.1.7

Other Approvals

This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS400F has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
RUGGEDCOM RS400F
Installation Manual, 02/2020, C79000-G8976-1341-04
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Informa-
tion Products
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Description
Enclosure
Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Certification
6.1.6 RoHS
https://support.indus-
Test Levels
±8 kV
±15 kV
20 V/m
±4 kV at 2.5 kHz
±4 kV
±4 kV
±4 kV
Severi-
ty Lev-
els
4
4
 
 
4
4
4
35