The following is the pin-out description for the RS485 insulated terminals:
Figure 4.11
4.4.5

Connecting Multiple RS485 Devices

Each RS485 port can communicate with multiple RS485 devices by wiring devices to-
gether in sequence over a single twisted pair with transmit and receive signals on the
same two wires (half duplex). For reliable, continuous communication, adhere to the
following guidelines:
The following shows the recommended RS485 wiring.
RUGGEDCOM RS400F
Installation Manual, 02/2020, C79000-G8976-1341-04
1
2
3
Serial Insulated Terminal Port
To minimize the effects of ambient electrical noise, use shielded cabling.
The correct polarity must be observed throughout a single sequence or ring.
The number of devices wired should not exceed 32, and total distance should be
less than 1219 m (4000 ft) at 100 kbps.
The Common terminals should be connected to the common wire inside the
shield.
The shield should be connected to earth ground at a single point to avoid loop
currents.
The twisted pair should be terminated at each end of the chain.
Communication Ports
4.4.5 Connecting Multiple RS485 Devices
 
Terminal
1
2
3
Common (Isolated Ground)
Description
Positive
Negative
25