Zone Interface Function - Haes Esento Eclipse ECL-2 Installation, Commissioning & Operating Manual

En54 approved 2-4 zone conventional control panel
Table of Contents

Advertisement

4
3
4
4
Conventional sounder circuit functional options
This option is used to programme each of the conventional sounder circuits on the main circuit board with
custom reponses as below.
Enter the above code and press ENTER. Then use button 1 to select the sounder
circuit to be programmed (indicated by a steady fire zone LED) as per table.
With the required sounder LED lit, press the ENTER button. Fire zone LED 1 will now
pulse. This indicates setting up function 1 (resets on silence alarms) for the selected
circuit. Use button 1 to scroll to the required function, indicated buy pulsing fire LEDs 1- 4 as per table
below.
Fire LED
LED 1
(pulsing)
Resets on
Function
Silence
Alarms
Amber
fault LED
OFF
(default
setting)

ZONE INTERFACE FUNCTION

This is a special setting to configure the last zone on the panel, (i.e. zone 2 on the ECL-2 or zone 4 on the
ECL-4), to be used for interconnection from other control panels.
The function is enabled by setting switch 2 on the 3 way DIL switch located on the main PCB to the 'ON'
position.
With switch 2 in the 'ON' position, the last zone becomes;
1. 1.
Non latching &
Non latching &
2. 2.
Non aux operating.
Non aux operating.
Note:
If the control panel is also set to Twin Wire mode (Switch 1 'ON') and sounders are connected to the
interface zone circuit, the following sounder operation will apply:
A fire (470Ω) signal to the interface zone will NOT operate the sounders connected to that Twin Wire circuit.
All other conventional (SNDR1 & SNDR2) and Twin Wire zone sounders will operate as normal.
A fire (470Ω) signal to any other zone will
operate ALL conventional (SNDR1 & SNDR2)
and Twin Wire sounder circuits, including the
sounders connected to the interface zone, as
normal.
Example connection
Eclipse Installation, Commissioning & Operating Manual
LED 2
LED 3
Activates
Activates
on
on Class
Evacuate
Change
ON
OFF
SETUP & PROGRAMMING
Use button 2 to change the response
LED 4
to ON or OFF, indicated by the amber
fault LEDs.
Activates
Then use button 1 again to scroll to
on Alert
the next function if required.
Press the ENTER button to return
OFF
back to sounder circuit selection,
indicated by a steady fire LED.
1
2
ZONE2 ZONE3 ZONE4
+ - + -
+ -
PANEL 1
Approved Document Ref: UI-ECL-01 Issue 8.0
25
LED 1
LED 2
SNDR1
SNDR2
(Main
(Main
PCB)
PCB)
3
4
5
6
7
ON
1
2
3
3K3
470
C NC NO
C NC
NO
FAULT
FIRE
(optional)
PANEL 2

Hide quick links:

Advertisement

Table of Contents
loading