Configure Profinet Settings Via The Tia Portal - Siemens SINAMICS V90 Application Description

Speed control via profinet
Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

3 Basics
3.2 Basic parameter configuration regarding SINAMICS V90 PN
3.2.3

Configure PROFINET settings via the TIA Portal

3.2.3.1 Configure SINAMICS V90 PN
The PROFINET settings of SINAMICS V90 PN can be configured in the TIA Portal
as follows:
1. Create a new project and switch to project view.
2. Install the V90 PN GSD file.
Installation of V90 PN GSD file is only necessary for TIA Portal prior to
NOTE
V14.
For the GSD file, you can download from following internet site:
https://support.industry.siemens.com/cs/ww/en/view/109737269
3. Find the GSD file and select it. Press the "Install" button to install it.
4. Click the node "Devices & networks" from the device tree on the left side.
Speed control with SINAMICS V90 and S7-300 via Profinet
Entry-ID: 109743898,
V1.0,
07/2016
10