Mstr Global Read Example - ICC MBP-100 Instruction Manual

Modbus plus multiprotocol network gateway
Table of Contents

Advertisement

Address
40200
40201
40202
40203
4.
In this case, we are accessing four registers, so set the bottom portion of
the MSTR instruction ("number of registers") to 4. In the case of MSTR
writes, this number cannot be greater than 100 by definition.
5.
Initiate the write command by closing internal relay 1. The data at registers
40200, 40201, 40202, and 40203 will be written to registers 1, 2, 3 and 4,
respectively, of the MBP-100 located at network address 32.

15.5 MSTR Global Read Example

The following example demonstrates how to use the MSTR instruction to read
32 words of global data from an MBP-100 located at Modbus Plus network
address 10.
1.
Set up a ladder logic program as shown in Figure 37.
2.
Set the top portion of the MSTR Instruction to 40070. This will be the
starting address of the MSTR Control Block. Set the control block registers
to the following values:
Address
40070
MSTR function (global read)
40071
Error code
40072
Number of consecutive registers to read
40073
Number of words available to read
40074
Destination node address
40075
Master node address
3.
Set the middle portion of the MSTR instruction to 40300. This will be the
starting address of the MSTR data area. This is the location that will
contain the data returned from the MSTR global data read transaction.
Address
40300
Value at offset 0 in global data from network address 10
40301
Value at offset 1 in global data from network address 10
:
40300+n
Value at offset n in global data from network address 10
:
40331
Value at offset 31 in global data from network address 10
Value to write to register 1 @ network address 32
Value to write to register 2 @ network address 32
Value to write to register 3 @ network address 32
Value to write to register 4 @ network address 32
Description
Value
Value
:
:
68
Register Value
6
Read Only
32
Read Only
10
1