The RS485 port and the ASD1 port of the gateway are internally shared,
which means that they both cannot be active simultaneously. Also, the
RS485 port's configuration has priority over that of the ASD1 port: if any
protocol is assigned to the RS485 port, then the ASD1 port will be
automatically disabled. Note, however, that the ASD2 and ASD3 ports will
at all times operate independently of all other network ports.
All parameter writes use the drive's RAM / EEPROM data write ("W")
command. For all writes that target the drive's EEPROM, be sure to follow
Toshiba's guidelines regarding the number of times a specific parameter
can be written without risk of EEPROM damage.
The drive response timeout (in seconds) is assigned via the designated
port's "Timeout" selection. If "0" is chosen (an invalid timeout time), the
gateway will use a 1s timeout by default.
Network characteristics selections
Baud rate: 2400 / 4800 / 9600 / 19200 / 38400 bps
o
Parity: odd / even / none (1 stop bit) / none (2 stop bits)
o
Point parameter number entry radix is hexadecimal (e.g. 10 = 0x0010 or
16
)