Suction Line Filter

Figure 87. Suction line filter installation: 20 to 60 Ton
units
Minimum 16" for CSHD straight
unobstructed piping between the
Suction Filter/Drier and the Tee

Fuse Replacement Data

Table 45. Fuse replacement selection
Fuse Description
Condenser Fan Fuse
(1F1-1F3 on 20 - 30 Ton)
(1F1-1F6 on 40 - 60 Ton)
Control CKT Fuse 1F7
Compressor Protector Fuse
1F8 on 20 - 60 ton
1F9 on 40 - 60 ton
Control Circuit Fuse 1F1
Compressor Protector Fuse 1F2 - 1F3
Condenser Fan Fuse
1F4-1F9
Condenser Fan Fuse
1F4-1F9
Transformer Fuse
1F12 - 1F13
SS-SVX11K-EN
Figure 88. Suction line filter installation: 80 to120 Ton
units
Minimum 25" for CSHN straight
unobstructed piping between the
Suction Filter/Drier and the Tee
Unit Voltage
Unit Size
200/230
20-60 Ton
460/575
380/415
20 - 30
All
40 - 60
20 -60 Ton
All
80 - 120
All
80 - 120
All
200 V
230 V
80
460 V
575 V
200 / 230 V
100 - 120
460 V
575 V
200 V
All
230 V
460 V
M M a a i i n n t t e e n n a a n n c c e e
25" min
Fuse Type
Fuse Size
25 Amp
Class RK5
15 Amp
3.2
Class CC FNQ
R
6.25
6 Amp
ABC - 6
Class CC FNQ-R
10 Amp
ABC - 6
6 AMP
30 Amp
25 Amp
Class RK5
20 Amp
15 Amp
35 Amp
25 Amp
Class RK5
20 Amp
6 Amp
FNQ-R
5 Amp
4 Amp
125