Trane RAUJ-C20 Installation, Operation And Maintenance Manual page 33

Split system
Table of Contents

Advertisement

Figure 22. Evaporator chiller — 40 ton
WITH INSULATION
2 x 2 3/8" VICTAULIC (P5 & P6)
P6
P5
SS-SVX11K-EN
1 3/16"
17 15/16"
1 3/8"
2 1/8"
7 7/16"
40 TON BRAZED PLATE HEAT EXCHANGER
ACCESSORY DRAWING
NOTES:
1. THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
2. HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH
SUPPLIED FASTENERS
3. INSULATIONSHOULD BE INSTALLED AFTER INSTALLING
LEGS & REFRIGERANT TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST
HEAT WHEN BRAZING REFRIGERANT LINES
4. INSTALL INSULATION SIDE PIECES FIRST THEN WRAPPER
TRIMMING
)
5. USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
6. WATER CONNECTIONS ARE GROOVED (VICTAULIC)
7. REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL
BRAZE MATERIALS. SEE IOM BRAZE PROCEDURE.
8. 1/2" NPT F5 CONNECTION SUPPLIED ON EXT'S 04 THRU 06 ONLY
BRAZED PLATE HEAT EXCHANGER REMOTE CHILLER EVAPORATOR OPTION
OPTION INCLUDES:
1 - BRAZED PLATE HEAT EXCHANGER - SHIPS SEPARATE FROM RAUJ
CONDENSING UNIT
1 - INSTALLATION KIT, TO INCLUDE:
2 - MOUNTING BRACKETS
1 - INSULATION KIT
1 - MOUNTING BRACKET & INSULATION KIT INSTALLATION INSTRUCTIONS
1 - WATER CONNECTION KIT WITH PIPING STUBS, Y CONNECTOR, STRAINER,
VICTAULIC CONNECTIONS WITH GASKETS,
WATER FLOW SWITCH
1 - WATER CONNECTION KIT INSTALLATION INSTRUCTIONS
INSTALLATION ADDITIONALLY REQUIRES:
RAUJ REMOTE EVP CONTROL PANEL WITH LEAVING WATER TEMPERATURE
SENSOR, FREEZE-STAT, AND INSTALLATION INSTRUCTIONS - ALL INCLUDED
WITH REMOTE EVP CONTROL PANEL
4 - FIELD PROVIDED 7/16" BOLTS FOR SECURING BRAZED PLATE HEAT
EXCHANGER TO PERMANENT MOUNTING SURFACE
2 - FIELD PROVIDED 1/2" - 14 NPTE PLUGS, STAINLESS STEEL OR PVC
FIELD PROVIDED TEFLON TAPE FOR SEALING 1/2" PIPE PLUGS
FIELD PROVIDED WATER STRAINER PLUG OR BLOW DOWN VALVE
FIELD PROVIDED TEE FOR INSTALLING WATER FLOW SWITCH
FIELD PROVIDED 2" VINYL TAPE FOR SEALING INSULATION SEAMS
SEE IOM FOR INSTALLATION DETAIL
2 x 1 3/8" ODF
7/8" DEPTH
3 15/16"
(F1 & F2)
20 11/16"
17 15/16"
2 x 1/2" ODF
5/8" DEPTH
(F1 & F2)
1 3/8"
1 1/16"
D D i i m m e e n n s s i i o o n n s s a a n n d d W W e e i i g g h h t t s s
(
MAY REQUIRE
2 13/16"
F2
F1
11"
5 1/2"
F3
F5
F4
4 13/16"
6 7/8"
SEE NOTE 8
1 3/8"
9 9/16"
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents