Trane RAUJ-C20 Installation, Operation And Maintenance Manual page 124

Split system
Table of Contents

Advertisement

M M a a i i n n t t e e n n a a n n c c e e
Table 43. Compressor circuit breakers (200-230 volts) (continued)
Voltage
Unit
200
50 Ton
230
200
60 Ton
230
200
80 Ton
230
200
100 Ton
230
200
120 Ton
230
Table 44. Compressor circuit breakers (460-575 volts)
Unit
20 Ton
25 Ton
30 Ton
40 Ton
50 Ton
60 Ton
80 Ton
100 Ton
120 Ton
124
Must Hold
1A / 2A
1B / 2B
57.1
63.1
51.4
57.1
69.3
69.3
59.4
59.4
73.7
73.7
63.1
63.1
73.7
73.7
63.1
63.1
105
105.2
90.7
90.7
Voltage
1A / 2A
460
575
460
575
460
575
460
575
460
575
460
575
460
575
460
575
460
575
1C / 2C
1A / 2A
-
65.7
-
59.2
-
79.7
-
68.3
73.7
84.7
63.1
72.5
105.2
84.7
90.7
72.5
105.2
121
90.7
104.3
Dial Setting
1B / 2B
20.8
20.8
17.7
17.7
20.8
24.9
17.7
21.4
28.5
28.5
25.9
25.9
20.8
20.8
17.7
17.7
22.6
24.9
19.1
21.4
28.5
28.5
25.9
25.9
28.4
28.4
22.7
22.7
28.4
28.4
22.7
22.7
41.6
41.6
33.3
33.3
Must Trip
1B / 2B
1C / 2C
72.5
-
65.7
-
79.7
-
68.3
-
84.7
84.7
72.5
72.5
84.7
121
72.5
104.3
121
121
104.3
104.3
1C / 2C
-
-
-
-
-
-
-
-
-
-
-
-
28.4
22.7
41.6
33.3
41.6
33.3
SS-SVX11K-EN