Table 32. Thermal expansion valve manufacturer settings - no bleed — Danfoss
Standard off the shelf nominal valve settings
Body size
Valve
TGEL 3.5 TR
TGEL 4.5 TR
TGEL 6.5 TR
TGE 10
TGEL 9 TR
TGEL 13 TR
TGEL 15 TR
TGEL 19 TR
TGE 20
TGEL 23 TR
TGEL 31 TR
TGEL 35 TR
TGE 40
TGEL 46 TR
Information in tables above is approximate and
intended to simplify field adjustment by presetting
valves to approximately 18°F superheat for DX evap
coils and 15°F superheat for EVP chillers. Actual
operating superheat will typically be less than 18°/15°F
and varies depending on many factors including those
listed above. Superheat gradient (superheat change
per turn) is also approximate and will not be constant
throughout the valve adjustment range. Check
superheat after startup to confirm proper control.
Tag or mark valve to keep a record of any field
adjustments.

Adding Preliminary Charge

1. Leak check must be completed and system
evacuated.
2. Verify that oil levels are near or above the top of all
compressor sight glasses.
W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . V V e e r r i i f f y y t t h h a a t t n n o o
p p o o w w e e r r i i s s p p r r e e s s e e n n t t w w i i t t h h a a v v o o l l t t m m e e t t e e r r . .
3. Insure field supplied unit disconnect is "OFF". Then
verify that the unit 1S2 115 volt control circuit
switch is "OFF" and that reset relays 1K21 & 1K22
have been unplugged to prevent inadvertent
compressor starts.
108
CW turns
SHT, °F
available
4
14.4
7
Superheat
CCW turns
change per
available
turn
4.5°F
3
3
4
4. Turn field supplied unit disconnect "ON" to energize
crankcase heaters. Verify crankcase heaters are
operating.
5. Verify that discharge, suction, and liquid line
service valves are open. Liquid line service valve
must be closed 1/4" turn from full open to allow for
fan pressure switch operation.
6. If system is equipped with hot gas bypass, insure
hot gas bypass is closed and remains closed during
charging.
7. Refer to table below for the charge estimate for the
condensing unit circuit and piping at the
appropriate piping length.
Table 33. Approximate charge per circuit (lbs)—
condensing unit and lines only
(does not include evaporator)
Total Interconnecting Line Length (ft)
Unit
Size
50
20
19
25
25
30
25
40
25
50
25
60
24
80
49
100
52
120
55
Field adjust
Field adjust
for 18°F (DX
for 15°F
evap coil)
(EVP only)
.75 CW
1.25 CW
.25 CW
100
150
25
32
37
50
38
50
37
50
38
50
36
48
69
88
73
94
76
98