Compressor Start-Up(All Systems) - Trane RAUJ-C20 Installation, Operation And Maintenance Manual

Split system
Table of Contents

Advertisement

N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
E E x x c c e e s s s s i i v v e e l l i i q q u u i i d d a a c c c c u u m m u u l l a a t t i i o o n n i i n n t t h h e e s s u u c c t t i i o o n n l l i i n n e e s s
c c o o u u l l d d r r e e s s u u l l t t i i n n c c o o m m p p r r e e s s s s o o r r d d a a m m a a g g e e . .
D D o o n n o o t t a a l l l l o o w w l l i i q q u u i i d d r r e e f f r r i i g g e e r r a a n n t t t t o o e e n n t t e e r r t t h h e e s s u u c c t t i i o o n n
l l i i n n e e . .
8. At the liquid line angle valve add as much R-410A
LIQUID as possible up to, but not exceeding, that
listed in
Table 33, p.
108. Depending on conditions,
it could not be possible to add more than 60% of the
charge listed in the table. This will be adequate for
compressor startup. More charge will be added
after compressors are started. Use an accurate
scale to measure and record the preliminary
amount of R-410A added to each circuit.
9. Do not add refrigerant in the suction line at this
time to prevent excessive refrigerant in the low side
prior to compressor startup.
Compressor Start-Up
(All Systems)
Table 34. Minimum starting ambient temperature
Minimum Starting Ambient
Standard Units
Unit
With
No
Size
HGBP
HGBP
20-60
45
80-120
45
(a)
Minimum starting ambients in degrees F and is based on the unit
operating at minimum step of unloading and 5 mph wind across
condenser.
1. Review "Adding Preliminary Charge" section and
confirm all steps were completed.
N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s c c o o u u l l d d r r e e s s u u l l t t i i n n
c c o o m m p p r r e e s s s s o o r r d d a a m m a a g g e e . .
K K e e e e p p c c r r a a n n k k c c a a s s e e h h e e a a t t e e r r s s o o n n w w h h e e n n e e v v e e r r r r e e f f r r i i g g e e r r a a n n t t i i s s
i i n n t t h h e e s s y y s s t t e e m m . .
I I f f c c r r a a n n k k c c a a s s e e h h e e a a t t e e r r s s h h a a v v e e n n o o t t b b e e e e n n o o n n w w i i t t h h
r r e e f f r r i i g g e e r r a a n n t t i i n n t t h h e e s s y y s s t t e e m m , , t t u u r r n n t t h h e e c c r r a a n n k k c c a a s s e e
h h e e a a t t e e r r s s o o n n f f o o r r a a m m i i n n i i m m u u m m o o f f 2 2 4 4 h h o o u u r r s s b b e e f f o o r r e e
s s t t a a r r t t i i n n g g c c o o m m p p r r e e s s s s o o r r s s . .
N N o o t t e e : : Initial compressor start-up is best done above
70°F outdoor temperature with ample evaporator
load (at least 70°F return air and 350 CFM/Ton)
N N o o t t e e : :
Table 34, p. 109
gives the minimum starting
temperatures for both "Standard" & "Low"
Ambient units
SS-SVX11K-EN
(a)
(°F)
Low Ambient Units
With
HGBP
No HGBP
40
10
0
40
10
0
I I m m p p o o r r t t a a n n t t : : Do not attempt to charge the system with
the low ambient dampers and/or hot gas
bypass operating (if applicable). Disable
low ambient dampers in the "Open"
position (refer to the "Low Ambient
Damper Adjustment" section) and verify
hot gas bypass is not operating before
proceeding.
2. On units with dual circuits, work on only one circuit
at a time. See tables in Compressor Sequencing
section for the compressor sequencing and
Operating Principals chapter Component Location
illustrations for their location..
3. Compare the amount of preliminary charge added
in the proceeding section to the table in that section
for condensing unit and piping only. Up to 20%
more charge than listed in that table may be
required to fully charge the circuit, depending on
the evaporator design. Have adequate R-410A
available to complete charging as described in the
following steps.
4. Attach a thermocouple type temperature sensor on
the liquid line close to the liquid line service valve.
To insure an accurate liquid temperature reading,
clean the line where the sensor is attached. After
securing the sensor to the line, insulate the sensor
and line to isolate it from the ambient air.
5. Attach a set of service gauges onto the suction and
discharge gauge ports.
6. Check the low side pressure. The low pressure
cutout (4S3, 4S4) opens below 58 psig and closes
above 78 psig. If the low side pressure is less than
78 psig, refrigerant may need to be added to the
suction line before starting the compressor(s).
Slowly meter into the suction line only as much R–
410A as needed to make the low pressure cutout
from the VAPOR charging connection. If possible,
plan to use this entire refrigerant bottle on the same
unit in order to minimize fractionalization. Use an
accurate scale to measure and record the amount of
R-410A added.
W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . V V e e r r i i f f y y t t h h a a t t n n o o
p p o o w w e e r r i i s s p p r r e e s s e e n n t t w w i i t t h h a a v v o o l l t t m m e e t t e e r r . .
7. Switch the field supplied unit disconnect "OFF".
Open the unit control box and plug in the reset
relay (1K21 or 1K22) for the circuit being started
only.
8. This charging procedure is more accurate at higher
S S t t a a r r t t - - U U p p
109