Full Gauge Controls MT-531Ri plus Quick Start Manual

Full Gauge Controls MT-531Ri plus Quick Start Manual

Temperature and humidity digital controller with serial communication

Advertisement

Quick Links

1. DESCRIPTION
MT-531Ri plus is an instrument that indicates and controls the environment temperature and
humidity, indicated for low and average relative air humidity (from 20 to 85%, without condensation) and
temperature of -10 to 70ºC. Its sensors of temperature and humidity are joined in an only bulb, that
reduces the space in wiring of the installation.
The instrument has serial communication for connection with the
Product complies with UL Inc. (United States and Canada).
Producto de conformidad con CE (Unión Europea) y UL Inc. (Estados Unidos y Canadá).
2. APPLICATION
• Poultry farm
• Humidificators/dehumidificators
• Grains drying
• Laboratories
• Surgical rooms
• Climatized cellars
• Information technology centers
3. TECHNICAL SPECIFICATIONS
- Power Supply:
MT-531Ri plus - 115 or 230 Vac ±10%(50/60 Hz)
MT-531RiL plus - 12 or 24 Vac/dc
- Control Temperature:
-10 to 70.0 ºC (with resolution of 0.1°C)
14 to 158 ºF (with resolution of 1°F)
- Control Humidity:
20 to 85%RH (with resolution of 0.1%UR)
- Load current:
5(3)A/250Vac 1/8HP (each output)
- Dimensions:
71 x 28 x 71 mm
- Operation temperature:
0 to 50°C
32 to 122°F
- Operation humidity:
10 to 90% RH (without condensation)
4.4 - Parameters description
Fun
Access code: 123 (one hundred and twenty-three)
T
hermostat operation mode (THERM output)
Minimum setpoint allowed to the user (thermostat)
Maximum setpoint allowed to the user (thermostat)
Control differential (hysteresis) of the thermostat
Minimum delay to turn the thermostat output on
Humidistat operation mode (HUMID output)
Minimum setpoint allowed to the user (humidistat)
Maximum setpoint allowed to the user (humidistat)
Control differential (hysteresis) of the humidistat
Minimum delay to turn the humidistat output on
Humidity output (time on)
Humidity output (time off)
Auxiliary output operation mode (AUX)
Minimum setpoint allowed to the user (AUX output)
Maximum setpoint allowed to the user AUX output
Control differential (hysteresis) of the AUX output
Minimum delay to turn the AUX output on
AUX output (time on)
AUX output (time off)
Low room temperature alarm
High room temperature alarm
Low room humidity alarm
High room humidity alarm
Minimum delay to turn the AUX output on (alarm mode)
Buzzer operation mode
Acting point of temperature Buzzer (inferior limit)
Acting point of temperature Buzzer (superior limit)
Acting point of
humidity
Buzzer (inferior limit)
Acting point of
humidity
Buzzer (superior limit)
Buzzer time on
Buzzer time off
Inhibition time of Buzzer during electrical supply
Display mode
Temperature display offset
Humidity display offset
Network equipment address RS-485
MT-531Ri plus
TEMPERATURE AND HUMIDITY DIGITAL
CONTROLLER WITH SERIAL COMMUNICATION
Ver. 01
®
SITRAD
via Internet.
Description
(
)
4. CONFIGURATIONS
4.1 - Temperature and humidity adjust (SETPOINT):
- Press
SET
for 2 seconds until
temperature for THERM output will appear.
- Use the keys
and
to change the value and then press
- Now
and adjusted humidity for HUMID output will appear.
- Use the keys
and
to change the value and then press
- If the parameter F14 is configured as thermostat or humidistat the following message will appear:
or
.
- Use the keys
and
to change the value for theAUX output and then press
4.2 - Parameters configuration
- Access the function F01 pressing simultaneously the keys
, releasing after that. Soon it will appear
- Use the keys
and
to enter acess code (123) and, when ready press
- Use the keys
and
to access the desired function.
-After selecting the function, press
- Use the keys
and
to change the value, and when ready, press
value and return to the menu of functions.
- To leave the menu of functions and return to normal operation, press
CELSIUS
Min.
Max.
Unit
Satandar
-99
999
-
-
0 - refrig.
1 - heat
-
0 - refrig.
-10.0
70.0
°C
-10.0
-10.0
70.0
°C
70.0
0
15
20.0
°C
0
999
seg.
0
0 - dehum.
1 - hum.
-
1 - hum.
0 - dehum.
0
100
%RH
0
0
100
%RH
100
0
20.0
%RH
5
0
999
sec.
0
0
999
sec.
5
0
999
sec.
5
0
5
-
5
0
100
-
0
0
100
-
100
0
20.0
-
5
0
999
sec.
0
0
999
sec.
5
0
999
sec.
5
-10.0
70.0
°C
-10.0
-10.0
70.0
°C
70.0
0
100
%RH
0
0
100
%RH
100
0
999
min.
0
0
1
-
1
-10.0
70.0
°C
-10.0
-10.0
70.0
°C
70.0
0
100
%RH
0
0
100
%RH
100
0
999
sec.
1
0
999
sec.
1
0
999
min.
0
-
0
2
0
°C
-5.0
5.0
0
%RH
-20.0
20.0
0
-
0
247
1
appears, then release it. The indication
to record it.
SET
SET
again.
and
, and then press
SET
SET
(short touch) to visualize the value configured for that function.
SET
SET
SET
SET
SET
SET
FAHRENHEIT
Mín
Máx
Unid
Padrão
-99
999
-
-
0 - refrig.
1 - heat
-
0 - refrig.
14
158
°F
14
14
158
°F
158
0
36
°F
3
0
999
seg.
0
1 - umid.
-
1 - hum.
0
100
%RH
0
0
100
%RH
100
0
20.0
%RH
5
0
999
sec.
0
0
999
sec.
5
0
999
sec.
5
0
5
-
5
0
100
-
0
0
100
-
100
0
20.0
-
5
0
999
sec.
0
0
999
sec.
5
0
999
sec.
5
14
158
°F
14
14
158
°F
158
0
100
%RH
0
0
100
%RH
100
0
999
min.
0
0
1
-
1
14
158
°F
14
14
158
°F
158
0
100
%RH
0
0
100
%RH
100
0
999
sec.
1
0
999
sec.
1
0
999
min.
0
0
2
-
0
-9
9
°F
0
-20.0
20.0
%RH
0
0
247
-
1
UL-Underwriters Laboratories
and the adjusted
to record it.
SET
for 2 seconds until appearing
(short touch).
to confirm.
SET
SET
to memorize the configured
until appear
.

Advertisement

loading

Summary of Contents for Full Gauge Controls MT-531Ri plus

  • Page 1 Ver. 01 UL-Underwriters Laboratories 4. CONFIGURATIONS 1. DESCRIPTION MT-531Ri plus is an instrument that indicates and controls the environment temperature and 4.1 - Temperature and humidity adjust (SETPOINT): - Press for 2 seconds until appears, then release it. The indication...
  • Page 2 F25 - Minimum delay to turn the AUX output on (alarm mode) Green protector It is the minimum time that the AUX output will keep turned off, it means, the space of time between the MT-531Ri plus MT-531RiL plus 9 - 8 115V last stop ant the next start.
  • Page 3 , being the cable shield. Device used to establish the The terminal of distribution box must be connected to the respective terminals connection Full Gauge Controls’ ® each instrument. instruments with the Sitrad IMPORTANT According to the chapters from the IEC60364 standard:...