ABB SACE Emax E2.2 Installation, Operation And Maintenance Instructions For The Installer And The User page 40

Low voltage air circuit-breakers
Table of Contents

Advertisement

I Protection
t
I3
38 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
I protection protects against instantaneous short circuit.
When the activation threshold is exceeded, the protection trips within a fixed non-adjustable time.
Parameters
I
The user can set the intervention threshold.
Parameter
t3
Enable
I
Threshold I3
Description
By setting the threshold dip-switches to the Off position, the protection is disabled.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
IMPORTANT: The I3 threshold set must be higher than the I2
threshold. An incorrect configuration returns an alarm signal.
ABB | SACE Emax 2
Ekip Dip | 4 - Protections

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents