Placing Body onto Bracket and
Leveling Feet
See
Figure
4-5. Lift body (A) onto bracket (B).
1.
Keep body tight to the wall while lowering body
onto bracket. Verify bracket tabs (C) hook into
body pockets (D).
A
Figure 4-5. Mounting Bracket (1 of 2)
See
Figure
4-6. Align body slots (E) with wall
2.
bracket holes (F).
E
F
Figure 4-6. Mounting Bracket (2 of 2)
Install body to bracket with two M4x8 screws in
3.
each horizontal bracket brace. Start screws. Do not
tighten.
Check unit for plumb side to side. Adjust feet as
4.
necessary.
Verify unit is standing on feet with body resting on
5.
wall bracket.
IMPORTANT NOTE: Do not lift the body off the
bracket by over-lengthening the feet.
Verify there is minimum 1.75 in (4.45 cm) gap
6.
between the bottom of the body and the floor.
Installation Manual for Generac PWRcell Battery
C
D
B
009656
009656
Installing Generac PWRcell Battery
Tighten machine screws to bracket and torque to
7.
13 in-lbs.
Verify feet have not lifted from floor.
8.
Tighten feet jam nuts to lock them in place.
9.

Installing REbus wiring

DANGER
Electrocution. Put the Generac PWRcell Inverter into
Safety Shutdown before installing wiring. If there are any
other batteries connected to REbus, toggle their front
Battery Disconnect switches to OFF. Failure to do so
will result in death or serious injury.
WARNING
Equipment damage. Connect only to REbus-compatible
devices. Never connect to any other power source.
Connecting to other power sources could result in
equipment damage.
WARNING
Equipment damage. Never connect REbus conductors to
ground. Connecting Rebus condutors to ground could
result in equipment damage.
When installing REbus wiring:
Wiring must be installed in accordance with Article
706 in the NEC.
Wiring must comply with local electrical codes
Wiring must be grounded according to local codes.
When required, grounding is the responsibility of
the installer. For proper REbus communication,
ensure the enclosure is securely bonded to the
Generac PWRcell Inverter via the grounding bar in
the Generac PWRcell Inverter wiring compartment.
Wiring must be protected from exposed metal
edges by using appropriate bushings, fittings, and
restraints.
Wiring must adhere to specifications in
Table 4-1. Wiring Specifications
Specification
Min
Allowable wire size
10
Torque
13.3 (1.5)
Strip length
Temperature rating
.
(000606)
(000598)
(000607)
Table
4-1.
Max
Units
6
AWG
15.9 (1.8)
lb-in (N-m)
3/8 (10)
in (mm)
90
C
15