Location and Compliance
Note on DC Wiring and the NEC
Some electricians or installers may be unfamiliar with DC
wiring in a residential setting. Note the following:
•
NEC 215.12(C)(2) for correct DC wiring coloring.
•
NEC 210.5(C)(2) for identification of DC conduc-
tors carrying more than 50V.
Always adhere to applicable codes when marking and
installing DC conductors.
Table
3-2. For all REbus DC wiring observe the fol-
See
lowing coloring convention:
Table 3-2. REbus DC Wiring Coloring Convention
Wire
REbus + (RE+)
REbus - (RE-)
Ground (GND)
NOTE: Mark or flag all conductors as appropriate.
12
Color
Red
Black or Blue
Green or bare
Installation Manual for Generac PWRcell Battery