Condair GS Series Installation And Operation Manual

Condair GS Series Installation And Operation Manual

Gas steam humidifier

Advertisement

Important: Read and save these instructions. This guide to be left with equipment.
GS
Series
Installation and
Operation Manual
Includes installation, operation,
maintenance, and troubleshooting
information for your Nortec GSTC
gas steam humidifier.
1506222-N| 20 NOV 2015

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GS Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Condair GS Series

  • Page 1 Important: Read and save these instructions. This guide to be left with equipment. Series Installation and Operation Manual Includes installation, operation, maintenance, and troubleshooting information for your Nortec GSTC gas steam humidifier. 1506222-N| 20 NOV 2015...
  • Page 2 WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage. Be sure to read and understand the installation, operation and service instructions in this manual. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.
  • Page 3 SERIAL # Proprietary Notice This document and the information disclosed herein are proprietary data of Condair Ltd. Neither thisdocument nor the information contained herein shall be reproduced used, or disclosed to others without thewritten authorization of Condair Ltd., except to the extent required for installation or maintenance of recipient’s equipment.
  • Page 4: Table Of Contents

    Contents 4 General 77 Wiring Diagrams & Spare Parts 7 Installation Indoor Installation Locating and Mounting Gas Piping Combustion Air Requirements Exhaust Venting Installation As A Category I Appliance Installation As A Category III Appliance Electrical 25 Plumbing 28 Outdoor Installation 35 Operation Start-Up Procedure Take Out of Operation...
  • Page 5 Introduction CAUTION: General  The Nortec GS series must be kept clear and free of combustible materials, gasoline, and other flammable vapors and liquids.  The indoor GS humidifier located in an insulated space must be kept free and clear of insulating material.
  • Page 6 Regardless of selecting On/Off or modulating control method, Nortec humidifiers must have a closed circuit across its On/Off security loop control terminal to operate. Nortec highly recommends the use of a high limit humidistat and an air proving switch in series for this function. Figure 1: GSTC- 3 | GS Series Installation...
  • Page 7: General

     Check packing slip to ensure ALL material has been delivered.  All material shortages are to be reported to Condair within 48 hours from receipt of goods. Condair assumes no responsibility for any material shortages beyond this period. ...
  • Page 8 General Specifications The Nortec GS Series humidifier is a completely new patented design based on leading edge technology. The GS is designed to provide clean steam humidification at an economical price. The GS Series humidifiers are designed exclusively for humidification in ventilation systems or direct room humidification.
  • Page 9 -0.05 NATURAL 45,000 -0.05 700,000 -0.35 PROPANE 50,000 -0.35 MODEL GSTC 600 SPECIFICATIONS BLOWER FUEL INPUT (BTUH) STEAM CAPACITY (LBS/HR) MANIFOLD PRESS. IN W.C. SPEED 840,000 -0.05 NATURAL 45,000 -0.05 840,000 -0.35 PROPANE 50,000 -0.35 GS Series Installation | 6...
  • Page 10: Indoor Installation

    Locating and Mounting GS Series humidifiers are designed for floor mounting or on a GS stand (optional). The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and national codes should be consulted prior to final location and installation of the humidifier.
  • Page 11 Warning: Steam distributor on the built-on and remote mounted blower packs have a hot surface that could result in burns if touched. Condair recommends mounting at least 8 feet above the floor. Ambient temperature location for humidifier: 41ºF - 104ºF (5ºC - 40ºC).
  • Page 12: Gas Piping

    14” w.c. (3.5 kPa). Dissipate test pressure from the gas supply line before re-opening the manual shut off valve to the appliance. 9 | GS Series Installation...
  • Page 13 (manifold pressure). The minimum gas pressure shown is for the purpose of input adjustment. A 1/8" NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the appliance. GS Series Installation | 10...
  • Page 14: Combustion Air Requirements

    Known contaminates include halogens, ammonia, and chlorides, excessive dust, lime or dirt. Excessive exposure of electronics to the contaminants will also result in performance related problems. Contact Condair technical services if you have any questions. If contaminants exist, isolate the unit from the contaminated space.
  • Page 15: Exhaust Venting

    The maximum flue temperature is 400ºF for category I and category III installations. Normal operating range is 360 to 380ºF. Category I and III class can be used with sealed combustion option Category III class must be used with direct vent option. GS Series Installation | 12...
  • Page 16 Select vent material and clearance according to the max vent gas temperature. All horizontal runs must be adequately supported with hangers or straps to prevent sagging. The vent must terminate at a sufficient height above the roof to prevent blockage by expected snowfall. 13 | GS Series Installation...
  • Page 17 Figure 7: Vertical Venting Using B Type Figure 8: Vertical Venting Using B Type with Sealed Combustion GS Series Installation | 14...
  • Page 18 / horizontal run, Drain max 100 ft (30 m), (Note: Condensate slope 1/4 in./ft (2 cm/m). may require treatment, consult local codes) Figure 10: Vertical and Horizontal Venting Using BH Type With Sealed Combustion 15 | GS Series Installation...
  • Page 19 - 6 in from wall. Air Intake Connect to intake Drain with hose cuff and (Note: Condensate hose clamps may require treatment, (by others). consult local codes) Figure 11: Direct Vent Installation Figure 12: Vertical Co-Venting Using B Type GS Series Installation | 16...
  • Page 20: Installation As A Category I Appliance

    Installation As A Category I Appliance General The GS Series humidifiers have a fan-assisted combustion which operates with a non-positive vent static pressure when installed with the appropriate vent diameter. Category I appliances must be vented vertically or nearly vertically (see Figure 7, 8, 9, 10 & 11).
  • Page 21 45° elbow equals 5'. The vent run should be as direct as possible with no more than 6 elbows in the system. Contact Condair technical service if you have any questions This category installation may not be common vented with any other natural draft gas appliance or power assist appliance.
  • Page 22 The vent terminal must be installed in the same atmospheric pressure zone as the combustion air inlet of the humidifier. If this is not possible (as in cases of positive or negative room pressures) the humidifier should be installed with the sealed combustion or direct vent option. 19 | GS Series Installation...
  • Page 23: Electrical

    Controls are available from CONDAIR as accessories and can be ordered with the humidifier. Controls by others may also be used as long as they meet the criteria noted below. The following is a summary of the common types of controls that may be used with CONDAIR Gas Humidifiers.
  • Page 24 If both channels are demanding steam the humidifier will satisfy the lower demand signal. Table 4: Current and Breaker Requirements for GS Series Units Voltage (V) Rated Amps (A) Suggested Breaker (A)
  • Page 25 Figure 14: Primary 208-240 V 1 Phase Line Voltage Wiring To Unit GS Series Installation | 22...
  • Page 26 GS/GS-E SERIES EXTERNAL CONTROLS WIRING CONNECTIONS LOW VOLTAGE TERMINAL STRIP Diagram No. 2545435 Rev. A Jan. 29, 2009 Figure 15: GS Series External Controls and Wiring Connections Low Voltage Terminal Strip 23 | GS Series Installation...
  • Page 27 Check operation of all on/off controls before starting humidifier. Calibration of controls (on/off or modulation) in the field may be necessary due to shipping and handling. Verify humidistat accuracy before commissioning system. GS Series Installation | 24...
  • Page 28: Plumbing

    Verify with local codes and install if necessary. Figure 16: Plumbing Connections 25 | GS Series Installation...
  • Page 29 The GS Series of Gas-Steam humidifiers can develop steam pressures up to 12”w.c. to overcome duct and steam line pressures. An enclosed trap on the drain line prevents steam from going to drain. Duct pressures above 12”...
  • Page 30 1.75 ft 7 ft 0.8 ft 34 ft 3” 5 ft 2.5 ft 11 ft 1.1 ft 54 ft 4” 8 ft 4 ft 15 ft 1.6 ft 80 ft *Valve in full open position. 27 | GS Series Installation...
  • Page 31: Outdoor Installation

    All installations must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 in the United States or CSA B149.1Installation codes in Canada. CONDAIR cannot accept responsibility for installation code violations. Mounting NOTE: Whenever possible do not expose drain water within the outdoor cabinetry.
  • Page 32 Figure 18: GSTC Outdoor Typical Installation Rooftop with AHU Figure 19: GSTC Outdoor Typical Installation Rooftop without AHU 29 | GS Series Installation...
  • Page 33 Figure 20: GSTC Outdoor Clearance Figure 21: Roof Curb Dimensions GS Series Installation | 30...
  • Page 34 Refer to Figure 22 for details. Condair recommends that each Gas Fired Humidifier has its own regulator installed in line to the unit. The operating Natural Gas pressure supplied for the GS units must be in the range of 5-9” of Water Column and 10-14”...
  • Page 35 Exhaust Venting – Outdoor Units All required exhaust venting is provided with each GSTC Outdoor model, by Condair, including rain cap and storm collar. All venting components external to the unit are shipped with the unit and must be installed on site. Refer to Figure 24 for venting components.
  • Page 36 NOTE: If the GSTC is installed in a cold area, or if the unit is a GSTC Outdoor unit, avoid installing the drain directly under the humidifier. In cold ambient air, the warm drain water can evaporate into water vapor, which can damage the electronics inside the humidifier if that vapor is allowed into the unit. 33 | GS Series Installation...
  • Page 37 Steam lines can be routed to an air handler on the roof or pipe chased (external to the unit) through the rooftop to enter the building. All steam lines must be insulated to reduce losses. For steam line installation guidelines, consult the distribution system installation manual (Steam Distributor Installation Manual). GS Series Installation | 34...
  • Page 38: Operation

    Water Management The GS Series of humidifiers is equipped with a unique float chamber water level monitoring device. Two magnetic floats (one is a backup) measure 5 different water levels in the humidifier for proper operation.
  • Page 39: Start-Up Procedure

    At the completion of the test, the float chamber will indicate middle float position (green LED) and the unit will go into standby mode until a demand signal is received. Proceed to the safety shut-off test. GS Series Installation | 36...
  • Page 40 The water in the tank will heat up and begin to boil, delivering steam to the distribution system. During the boiling sequence the water fill valve will periodically activate to replenish water that has evaporated from the tank. 37 | GS Series Installation...
  • Page 41 The humidifier will go into standby mode until the next call for humidity (demand rises above minimum %) at which time the unit will again begin the combustion sequence. GS Series Installation | 38...
  • Page 42 ____  Can condensate be trapped anywhere in the steam line? yes ___ no ___ Condensate Lines  Sloped back to drain  Trap is greater than 2” duct static pressure  Size of trap____________ 39 | GS Series Installation...
  • Page 43 Silica____ppm  Chlorides:_______ppm  pH:_______ NOTE: Failure due to chloride corrosion is not covered under Condair’s standard warranty if chloride concentration is allowed to reach elevated levels in the tank. Consult factory for more information. Electrical Installation  Comply with local regulations ...
  • Page 44: Scale Management

    You can even contact your municipality for your water condition or order the CONDAIR water test kit. NOTE: Water quality conditions resulting in component failures are not covered under CONDAIR’s standard warranty.
  • Page 45 40 ppm. NOTE: Failure due to chloride corrosion is not covered under Condair’s standard warranty if chloride concentration is allowed to reach elevated levels in the tank. Consult factory for more information.
  • Page 46: Fault Conditions

    A history of all faults is stored in memory of the software and can be viewed through the service level on the display. Refer to the keypad display menu structure at the end of the manual. 43 | GS Series Installation...
  • Page 47: Maintenance

    Periodic cleaning of the screens in the vent terminal (where applicable) is recommended. NOTE: Use only CONDAIR original parts to replace damaged or defective components. Failure to do so may cause improper operation of the humidifier and will void warranty.
  • Page 48 Gas Venting to condensate traps. Flue temp should be between 350-400ºF. Inspect for leaks. Ensure Direct Vent intake terminal is clear. Visual check that sensor is H/L Stack intact, wired and attached to Sensor the exhaust. 45 | GS Series Installation...
  • Page 49: Cleaning The Steel Tank

    Due to the presence of polymer gaskets around the heat exchanger, do not use any harsh cleaning chemicals. Please consult CONDAIR prior to using any chemicals. Once the lid has been replaced, fill the unit with water and examine for leaks.
  • Page 50: Servicing The Unit

    The control will attempt two additional ignition trials before going into lockout. The valve relay will be de- energized immediately, and the combustion blower will be turned off. Warning: Disconnect power before servicing this appliance. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. 47 | GS Series Installation...
  • Page 51 V model should read 300-1300 Ohms. Gas Valve Setting The gas valves used in the GS Series humidifier are negative-pressure-regulated valves. The valve setting listed on the product rating plate is shown relative to atmosphere – this setting will always remain constant.
  • Page 52: Component Replacement

    Consult factory prior to the replacement of any component. All service work must be performed by experienced and trained personnel. Only use original CONDAIR spare parts to replace defective components. Damage caused by non- approved parts is not covered under CONDAIR’s standard warranty.
  • Page 53 Undo the 2 screws that mount the gas valve/air inlet assembly to the blower and remove the assembly. Undo the 4 screws and remove the gas pipe connection from the inlet of the gas pressure regulating valve. GS Series Installation | 50...
  • Page 54 Squeeze both sides of the mounting bracket to release it from the slots in the support bracket behind the float chamber. Reverse the above sequence to install the new module. Leak test all water connections before re-commissioning the humidifier. Figure 36: Air Switch Replacement Figure 37: Float Chamber Replacement 51 | GS Series Installation...
  • Page 55 Anode Replacement Follow the steps in Cleaning the Steam Tank on page 46 to remove the clean-out port. Lift the corroded anode off the steel rod. Replace with a new anode. Re-attach the clean-out port. GS Series Installation | 52...
  • Page 56 Undo the two nuts securing the fill box to the face of the tank, then remove the fill box. Re-installation is carried out in the reverse sequence. Make sure the hoses are correctly secured with the hose clamps. Figure 42: Fill Box Replacement 53 | GS Series Installation...
  • Page 57 Unscrew the nuts on the heat exchanger and pull out the heat exchanger from the tank. Re-installation is carried out in the reverse sequence. Replace all seals with new ones. Figure 43: Heat Exchanger Assembly GS Series Installation | 54...
  • Page 58: Key Pad

    RH Limit : 40%RH LIM Set-P : 80 NOTE: If the humidifier is set to dual channel, the limiting Output : 305 lb/hr humidity sensor’s measured RH and the desired set point is also displayed. 55 | GS Series Installation...
  • Page 59 Proportioning status, the Blow Down rate percentage, the Time Prop. : On Drain Cool mode and the Float Check status. BD rate : 25 Drain Cool : Smart NOTE: See User Defined Settings to change these Float Ck : On parameters. GS Series Installation | 56...
  • Page 60 Humidity Demand Trend 100% This screen displays the humidity output over the past 4 hours. The current demand is also displayed numerically at the bottom of the screen. -4 hrs 0 hrs Demand: 50% Menu 57 | GS Series Installation...
  • Page 61 : Dual CH Dual CH Dual Channel (control and high limit). Multi Mode : StandAlone NOTE: In Dual Channel MOD Mode, a CNT Type : 0-10V LIM Type : 0-10V second Limiting control signal is required. GS Series Installation | 58...
  • Page 62 Short CD : Off 300s Short CD T : 300 Short CD T : 300 Time Prop : On NOTE: Short CD has to be turned On. Manual Cap. : 100 See above. ModBus Settings 59 | GS Series Installation...
  • Page 63 Settings submenu by pressing the menu key while RH Settings is highlighted in the Control Settings menu. CNT Set-P Sets the humidity setpoint value. The humidifier will attempt to maintain this humidity level in the space where the control transducer is installed. GS Series Installation | 60...
  • Page 64 100 to 0%. (Default = 15%) Limit Damping Sets the number of seconds the sensed RH must exceed the limit band before output is throttled down. (Default = 5 s) 61 | GS Series Installation...
  • Page 65 RH Alerts is set to on. RH Low Sets the RH level below which the humidity must fall before a warning is generated . Warning is only generated if RH Alerts is set to on. GS Series Installation | 62...
  • Page 66 Multi Unit Op. Range ModBus Settings Multi Unit Op. Range Full Out. Full Out. : 100 Full Out. :100 100 % Zero Out. 100 % Multi Unit Op. Range Zero Out. Full Out. :100 Zero Out. Zero Out. 63 | GS Series Installation...
  • Page 67 Remote Disable Allows unit to be disabled Modbus Settings Rem Disable remotely through the network. Parity : None1 Addr Timeout : 300 Rem Disabl : Off Rem Disabl : On GS Series Installation | 64...
  • Page 68 : Off a set interval of weighted hours. FTBD Time : 23:30 NOTE: See FTBD Time to set time of FTBD Hours : 100 Idle Mode : Idle Drain day and FTBD Hours to set interval. 65 | GS Series Installation...
  • Page 69 Drain Corr. : 100 correction adjusts the actual drain Float Ck : 23:30 duration by drain time. Increasing Date : 01/01/09 drain correction increases drain Time : 12:00:00 duration and decreasing correction decreases drain time. GS Series Installation | 66...
  • Page 70 : 23:30 Hour : 12 Hour : 12 the main screen. The time is set at Date : 01/01/09 Minute Time : 12:00:00 Time : 12:00:00 the factory. Unit Steam : lb/hr Language : English Contrast 67 | GS Series Installation...
  • Page 71 : English Dutch Contrast Contrast User Defined Setting Contrast Set the Total Controller’s LCD Float Ck : 23:30 display contrast. Date : 01/01/09 Time : 12:00:00 Unit Steam : lb/hr Language : English Contrast Contrast GS Series Installation | 68...
  • Page 72 Set time interval of the service Burner Disable 500 h Service Tm Service Tm :500 : 500 500 h reminder. Tank Drain Tank PreClean NOTE: Do not modify. Interval set Reset Error History from factory. Reset Serv. Reminder 69 | GS Series Installation...
  • Page 73 Resets service reminder. Burner Disable Reset Serv. Reminder Service Tm : 500 Tank Drain are you sure? NOTE: Service reminder should Tank PreClean only be reset after servicing. Reset Error History Reset Serv. Reminder Reset Serv. Reminder GS Series Installation | 70...
  • Page 74 HOUR:MINUTE Error Code Press the “?” for an explanation of the error code and access to the troubleshooting guide. Use the UP and DOWN arrow keys to navigate through the explanations and corrective action required. 71 | GS Series Installation...
  • Page 75 Service Relay Service Remote Test Remote Test Error Relay Service Remote Test Allows the user to test manually the remote fault indication. Three relays are available: • Steam Production • Service Needed • Humidifier Error GS Series Installation | 72...
  • Page 76: Troubleshooting

    RPM Verify blower control wiring connection. allowable tolerance. remains low. Check blower diagnostic test for abnormalities. Ensure no restriction on blower. Ensure no blockage of blower inlet. 73 | GS Series Installation...
  • Page 77 NBW: NO All burners have been The unit will not be BURNERS disabled via software. able to respond to AVAIL No burners are a demand until 1 or available for operation. more burners are enabled. GS Series Installation | 74...
  • Page 78 Check strainer on fill valve inlet. Investigate Check that drain valve, auxiliary the problem before drain valve or manual drain switch are not restarting unit. activated. Check fill valve using diagnostic output test. Consult factory. 75 | GS Series Installation...
  • Page 79 FAULT maintenance interval operate Unit requires servicing. Consult maintenance and 72hour window Is such a condition guide in the Condair manual. Service reminder must be cleared after maintenance. Refer to for cleaning manual. has expired. GS Series Installation | 76...
  • Page 80 Wiring Diagrams & Spare Parts 77 | GS Series Installation...
  • Page 81 Figure 44: GSTC 100-600 (110-120 VAC) Internal Wiring Diagram GS Series Installation | 78...
  • Page 82 Figure 45: GSTC 100-600 (208-240 VAC) Internal Wiring Diagram 79 | GS Series Installation...
  • Page 83 Figure 46: GS Series INDOOR Exploded View - Internal Component GS Series Installation | 80...
  • Page 84 Table 12: GS Series INDOOR Exploded View - Internal Components GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 Description Part # SP Sacrif. Anode Upgrade Kit,GS/SE,B-B+ 2570309 SP Clean-Out Door Kit,w/o 2548607 Anode,GS,B/B+ SP Sacrificial Anode Kit, GS/SE,B-B+...
  • Page 85 Table 12: GS Series INDOOR Exploded View - Internal Components - continued GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 Description Part # Igniter/flame sensor gasket 2549802 Hot Surface Igniter Replacement Kit 110 - 120V Models...
  • Page 86 Figure 47: GS Series INDOOR Exploded View - Cabinetry 83 | GS Series Installation...
  • Page 87 Table 13: GS Series INDOOR Exploded View - Cabinetry Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 Service Door Assembly Mini 2524439 Single 2524440 Double 2524441 Triple 2524458 Front Door Assembly 2535268 Recessed Handle...
  • Page 88 Figure 48: GS Series OUTDOOR Exploded View – Cabinetry 85 | GS Series Installation...
  • Page 89 Table 14: GS Series OUTDOOR Exploded View - Cabinetry Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 GSTC Processor Board Replacement 2544252 Driver board 2535504 Primary Transformer 2532672 110 - 120V Models 208-240V Models 2532673 Fuse for Primary transformer, 6.25 Amp...
  • Page 90 Figure 49: GS Stand Assembly Instructions 87 | GS Series Installation...
  • Page 91 Min drain pipe size (in/cm) 1 to 1.5 / 2.5 to 3.8 OD or larger Power supply requirements 120 volts a/c 208-240 volts a/c 1PH Steam Outlet size (in/cm) 1.75/4.4 3/7.6 3/7.6 4/10.2 4/10.2 4/10.2 GS Series Installation | 88...
  • Page 92  ...
  • Page 93 Warranty Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY),warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the media) are free from defects in material andworkmanship.
  • Page 94 U.S.A. 835 Commerce Park Ave Ogdensburg, NY 1366-2209 CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7 TEL: 1.866.667.8321 EMAIL: na.info@condair.com WEBSITE: www.condair.com U.S. Patent 5,816,496 Canadian Patent 2,203,332...