The next 32 input bytes are used for the actual Livelist data. Each address uses two bits. So the first two bits of
the first byte are for address 0, the next two bits of the first byte are for address 1 and so on. The bits are used
to indicate if the station is a slave device, master device or both.
Device:
Bit 1:
None
0
Slave Device
0
Controller
1
Both
1
Example:
If there is a master device on address 2, and a slave device on address 3, then the first byte
will be 0x60, because it will look like this:
Bit
7
6
Value
0
1
Address 3
This module also has 2 Output bytes. The first Output byte is used to select the Livelist of a specific Channel.
This selection can be read-back in the Input byte described above.
Hex
Meaning
80
Livelist of FO Channel
81
Livelist of Channel 1
82
Livelist of Channel 2
83
Livelist of Channel 3
84
Livelist of Channel 4
85
None
86
Livelist of this ProfiHub
FF
Livelist of all channels (entire network)
The next Output byte can be used to reset the Livelist. Write 0x01 to this Output byte to reset the Livelist.
3.2.11

Statistics (Short Format, Long Format )

Input Identifier byte: 0x30 (short format) or 0x31 (Long Format)
The next byte is used to display the current selection of statistics that it sends.
Hex
Meaning
00..7E
Statistics for device 0..126
7F
Statistics for undefined devices
80
Statistics of FO Channel
81
Statistics of Channel 1
82
Statistics of Channel 2
83
Statistics of Channel 3
84
Statistics of Channel 4
85
None
86
Statistics of this ProfiHub
FF
Statistics of all channels (entire network)
ProfiHub B2FOR+ / B4FOR+ User Manual | August 2019 | © PROCENTEC
Bit 0:
0
1
0
1
5
4
1
0
Address 2
Address 1
3
2
1
0
0
0
Address 0
0
0