Baldor VS1STS Series Installation & Operating Manual page 47

Ac microdrive
Table of Contents

Advertisement

Par
Description
No.
Brake Chopper Duty
P6-10
Cycle when Under
Temperature
Preset Speed Run Time
P6-11
On Enable
Preset Speed Run Time
P6-12
on Disable
MN767S
Table 7-7 Application Specific Parameters Continued
Range
0.0...20.0
0.0..600.0
0.0..600.0
Units
Default
This parameter defines the
duty cycle applied to the brake
chopper while the drive is in an
under temperature trip state. A
Brake resistor can be mounted
to the drive heat sink, and used
to warm the drive until the
correct operating temperature is
%
2.0
reached.
This parameter should be
used with extreme care, as
incorrect adjustment may result
in exceeding the rated power
capacity of the resistor. External
thermal protection for the
resistor should always be used
to avoid this risk.
Defines a time period for which,
following an enable signal
being applied to the drive,
the drive will run at the speed
S
0.0
programmed in Preset Speed
7 (P2-07). This feature can be
used on pumps to provide a
reverse spin on start up, to
avoid potential blockages.
Defines a time period for
which, following removal of
the enable (Run) signal and
the drive ramping to standstill,
the drive will then operate at
S
0.0
the speed set in Preset Speed
8 (P2-08). This feature can be
used in applications such as
underground PCP pumps to
provide unwind of the driveshaft
on stopping.