Par
Description
No.
Digital Output Control
P2-12h
High Limit
Digital Output Control
P2-12L
Low Limit
User Relay Output
P2-13
Function Select
Relay Output Control
P2-14h
High Limit
Relay Output Control
P2-14L
Low Limit
P2-15
Relay Output Mode
Zero Speed Holding
P2-16
Time
P2-17
Start Mode Select
7-4 Parameter Descriptions
Table 7-2 Parameter Group 2 - Extended Parameters Continued
Range
0.0 to 200.0
0.0 to P2-12h
0: Drive Enabled
1: Drive Healthy
2: Motor at Target Speed
3: Motor Speed >0
4: Motor Speed >= Limit
5: Motor Torque >= Limit
6: 2nd Analog Input >= Limit
0.0 to 200.0
0.0 to P2-14h
0: Normally Open
1: Normally Closed
0.0 to 60.0


 to5
Units
Default
With P2-11 = 4 to 6, Digital
%
100.0
Output 1 is set to Logic 1 (+24V
DC) when the value set in P2-
12h is exceeded, and returns to
Logic 0 (0V) when the selected
%
100.0
value reduces below the limit set
in P2-12L
Selects the function assigned to
the relay output.
0: Logic 1 when the drive is
enabled (Running)
1: Logic 1 When no Fault
condition exists on the drive
2: Logic 1 when the motor
1
speed matches the set point
speed
3: Logic 1 when the motor runs
above zero speed
Options 4 to 6 : the Digital
output is enabled using the
level set in P2-14h and
P2-14L
With P2-13 = 4 to 6, the User
Relay Output is set to Logic 1
%
100.0
(+24V DC) when the value set
in P2-14h is exceeded, and
returns to Logic 0 (0V) when the
selected value reduces below
the limit set in P2-12L
%
100.0
Inverts the operating status of
the User Relay
0: Logic 1 = Relay Contacts
Closed
-
0
1: Logic 1 = Relay Contacts
Open
The drive must be powered for
the contacts to close
Determines the time for which
the drive output is held at zero
Seconds
0.2
speed when stopping, before
the drive output is disabled.
Edge-r: Following Power on or
Auto-0: Following a Power
-
Auto-0
Auto 1 to 5: Following a Fault,
Explanation
reset, the drive will not
start if Digital Input 1
remains closed. The
Input must be closed
following a power on or
reset to start the drive.
On or Reset, the drive
will automatically start if
Digital Input 1 is closed.
the drive will make up
to 5 attempts to restart
at 20 second intervals.
The drive must be
powered down to reset
the counter.
MN767S