Baldor VS1STS Series Installation & Operating Manual page 39

Ac microdrive
Table of Contents

Advertisement

Par
Description
No.
2nd Analog Input
P2-33
Format
2nd Analog Input
P2-34
Scaling
Digital Speed Reference
P2-35
Scaling Control
P2-36
Analog Output Format
Extended Menu Access
P2-37
Code
P2-38
Parameter Lock
P2-39
Hours Run Counter
P2-40
Drive Type / Rating
MN767S
Table 7-2 Parameter Group 2 - Extended Parameters Continued
Range
 2= Digital
  = 0 to 10VDC
 2 = 4 to 20mA
 2 = 0 to 20mA
0 to 500.0
0: Disabled (No Scaling)
1: Scaled by P2-29
2: Scaled by P2-29, then bipolar
analog input added as an
offset
3: Scaled by P2-29 and by
bipolar analog input
  = 0 to 10V
 2 = 4 to 20mA
  = 10 to 0V
 2 = 20 to 4mA
0 to 9999
0: Unlocked
1: Locked
0 to 99999
N/A
Units
Default
Selects the format for the 2nd
analog input
-
 2
Selecting  2 sets the input
up as a digital input.
Scales the 2nd analog input by
%
100.0
the factor set in this parameter.
Active in Keypad mode (P1-07 =
1 or 2) and Master / Slave mode
only.
1: Actual Speed = Digital Speed
x P2-29
-
0
2: Actual Speed = (Digital
Speed x P2-29) + bipolar
analog reference
3: Actual Speed = Digital
Speed x P2-29 x bipolar
analog reference
Selects the analog output signal
-
 
format.
Defines the access code which
must be entered in P1-14 to
-
101
access parameter groups above
Group 1.
When locked, all parameter
-
0
changes are prevented.
Read
Indicates the number of hours
Hours
Only
for which the drive has run.
Read
Read only parameter, showing
-
Only
the drive type and power rating.
Parameter Descriptions 7-7