Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:
(Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)
Maximum Loop Voltage: 25VDC input.

Maximum Loop Current: 1.7mA

End of Line Resistor (EOLR) Value: 10K

Electrical Ratings for PGM3 Output:
Open Collector Output: Maximum Voltage 25VDC.

Maximum PGM Sink Current:

25mA (15.1VDC - 25VDC)
Physical (W x H x D)
Plastic Housing: 8 x 5-

Mounting: Plastic housing includes three keyhole slots

for triple gang boxes (see scale template on page 13);
Environmental
Operating Temperature: 0°C - 49°C (32°F - 120°F)

Humidity: Maximum 93% Non-Condensing

Indoor / dry location use only


TERMINAL DESCRIPTIONS

Configure all inputs and outputs using the Management
Center screen (located at www.NapcoNOC.com). Located
at the bottom of the StarLink radio PC board, the terminals
are described as follows:
TB1: PWR (+10 - 25VDC)
(Refer to section "STEP 4: APPLY POWER")
TB2: PWR GND (–)
(Refer to section "STEP 4: APPLY POWER")
TB3: PGM3 (–): Open collector output. PGM3 is nor-
mally on (active low). When it is triggered (for exam-
ple, a trouble is detected) it becomes open collector/
high. To have a zone dedicated to an StarLink radio
trouble, insert one side of the end of line resistor into
this PGM3 terminal, and wire the other side of the
resistor to the positive terminal of the zone.
TB4: IN 1 (+): Smart Channel input. Active high input
for wiring to the control panel bell output. When this
input detects a pulsing temporal 3 high, it sends a
Supervised Fire Input Wiring Option
6
8
Radio GND
-or-
(TB6 and
TB88)
10K
10K
C
TBL*
The EOLR must be installed and located within the control panel housing.
*Reverse polarity / energized state.
**Factory programmed options; may be changed at the NOC website (www.NapcoNOC.com)
2
50mA (up to 15VDC),
29
/
x 1½" (20.3 x 13.9 x 3.8cm)
64
To StarLink
5
7
-or-
Terminals
IN2 (TB5)
-or-
IN3 (TB7)
(Radio)
(Alarm Panel)
N/O
C
N/O
N/C
Alarm
StarLink
SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
Fire alarm; a pulsing temporal 4 (CO Alarm), a CO
alarm is sent. When used, these conductors must
be run in conduit (max 20 feet for Commercial Fire,
and 3 feet for Residential Fire). For this input to
report to a central station, the StarLink radio must
be configured with the central station telephone
number and correct reporting formats and codes.
For more information, see WI2140 located at
www.NapcoNOC.com.
TB5: IN 2 (+): Fire Trouble input**. Wire to FACP
trouble relay N/O with parallel 10K EOLR at FACP.
Note: Inputs IN 2, IN 3, IN 4 and IN 5 can be su-
pervised end-of-line resistor inputs that can be trig-
gered with N/O or N/C relay contacts.
common ground terminal GND (terminal TB13) to
the relay common. For these inputs to report to a
central station, the radio must be configured with the
central station telephone number and correct report-
ing formats and codes.
TB6: IN 2 (–): See TB5, above.
TB7: IN 3 (+): Fire Alarm input**. Wire to FACP Fire
Alarm relay N/O with parallel 10K EOLR at FACP.
TB8: IN 3 (–): See TB5 and TB7, above.
Secondary Telephone: RJ-45 socket for FACP DACT
connection.
Primary Telephone: RJ-45 socket for FACP DACT con-
nection.
TB9: IN 4 (+): Supervisory Alarm input**. Wire to
FACP Supervisory relay N/O with parallel 10K
EOLR at FACP.
TB10: IN 4 (–): See TB5 and TB9, above.
TB11: IN 5 (+):
Water Flow Alarm input**.
FACP Water Flow relay with parallel 10K EOLR at
FACP.
TB12: IN 5 (–): See TB5 and TB11, above.
TB13: GND: Earth ground terminal.
Ethernet: Connect the SLE Dual-Path radio communica-