Precautions during transportation

This section explains the precautions needed when transporting this product.
• When transporting the rack, check beforehand that the width of the route to be used is wider than
the rack.
• Use of a board may be necessary when there is a bump in the transportation route.
[Device]
• Because the maximum weight including the rack can be more than 1000kg, check that there is no
problem with the transportation route before moving it.
ex.) Type of floors on the route used to transport the device:
Check that the floor has enough load capacity to hold the device, and that casters do not sink
into the surface of the floor, or get hung up on the floor.
• Confirm that you can use the elevator when the device is transported to a upper or lower floor in a
building, and that the laden weight capacity of the elevator is more than the weight of the device.
• When transporting the device, push the lower part of the rack rather than the middle of the rack's to
keep the rack from falling. The barycentric position of the rack can be higher or lower than the
center of rack depending on where individual devices are installed.
Also, do not push on the sides. Doing so may lead the device to fall.
• If the center of the front door or the air vent opening is pushed, they can become deformed. Push
the corner of the door to move the rack.
• When the devices that are installed in the rack are taken from a cold area to a warm room, conden-
sation builds up inside of the device.
Adjust the room temperature so it does not exceed a 15°C rise an hour, in order to discourage the
build up of condensation.
Refer to the following table for information on condensation.
Relative
20
humidity
40
(%)
60
80
90
Room temperature
10
15
20
25
-7
-5
-3
1
-3
2
7
11
3
8
13
17
7
12
17
22
9
13
19
24
Board (steel plate etc.)
30
35
40
5
9
13
When room temperature is
25 °C and humidity is 60%,
16
20
24
the device will begin to
22
26
31
build up condensation if its
26
31
-
inside temperature is 17 °C
29
34
-
or less.
1 Precautions for Rack Installation and Use
Remarks
45