2.5

Rack connection

To expand the rack, connect another rack to the existing one (base rack). One expansion rack may be
mounted to the base rack.
For a maximum of two racks (40U type) including the base rack.
WARNING
• To reduce the risk of equipment damage and electric shock, switch off power for
the server unit and peripherals and unplug the power cable before connecting the
rack.
CAUTION
• Rack connection must be performed by at least two workers.
• If getting on the stepladder, note the fall from the stepladder.
• DO NOT put the foot on the rack when connecting the racks.
The recommended procedures are given below.
1
Remove the side panel of the base rack.
Unscrew the eight screws securing the side panel, and remove the panel. Do NOT lose the
screws they need to be used in Step 8.
Screw (M4)
2 Standard Rack (40U/24U)