6.4.6 To connect the refrigerant piping to the indoor unit
6.5 Connecting the electrical wiring
6.5.1 About connecting the electrical wiring
FTXP50~71M2V1B + FTXF20~71A2V1B + ATXF50~71A2V1B
Daikin room air conditioner
4P513661-8H – 2019.12
Flare tool for R32
(clutch type)
A
0~0.5 mm
5 Check that the flaring is properly made.
a
a
Flare's inner surface MUST be flawless.
b
The pipe end MUST be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
▪
Pipe length. Keep refrigerant piping as short as possible.
▪
Flare connections. Connect refrigerant piping to the unit using flare connections.
▪
Insulation. Insulate the refrigerant piping, interconnection cable and drain hose
on the indoor unit as follows:
c
a
b
f
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
g
Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1
Making sure the power supply system complies with the electrical
specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor unit.
4
Connecting the main power supply.
Conventional flare tool
Clutch type
(Ridgid-type)
1.0~1.5 mm
b
c
d
e
g
6
Installation
|
Wing nut type
(Imperial-type)
1.5~2.0 mm
Installer reference guide
33