6.4.6 To connect the refrigerant piping to the indoor unit

6.5 Connecting the electrical wiring

6.5.1 About connecting the electrical wiring

FTXP50~71M2V1B + FTXF20~71A2V1B + ATXF50~71A2V1B
Daikin room air conditioner
4P513661-8H – 2019.12
Flare tool for R32
(clutch type)
A
0~0.5 mm
5 Check that the flaring is properly made.
a
a
Flare's inner surface MUST be flawless.
b
The pipe end MUST be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
Pipe length. Keep refrigerant piping as short as possible.
Flare connections. Connect refrigerant piping to the unit using flare connections.
Insulation. Insulate the refrigerant piping, interconnection cable and drain hose
on the indoor unit as follows:
c
a
b
f
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
g
Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1
Making sure the power supply system complies with the electrical
specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor unit.
4
Connecting the main power supply.
Conventional flare tool
Clutch type
(Ridgid-type)
1.0~1.5 mm
b
c
d
e
g
6
Installation
|
Wing nut type
(Imperial-type)
1.5~2.0 mm
Installer reference guide
33