Pilz PNOZ m ES Powerlink Operating Manual
Pilz PNOZ m ES Powerlink Operating Manual

Pilz PNOZ m ES Powerlink Operating Manual

Configurable control systems pnozmulti 2

Advertisement

Quick Links

PNOZ m ES Powerlink
}
Configurable control systems PNOZmulti 2
Operating Manual-1003193-EN-05

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PNOZ m ES Powerlink

  • Page 1 PNOZ m ES Powerlink Configurable control systems PNOZmulti 2 Operating Manual-1003193-EN-05...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Commissioning General wiring guidelines Connecting the supply voltage Interface assignment Download modified project to the PNOZmulti system Connection example Section 7 Operation Messages Section 8 Technical Details Section 9 Order reference Product Accessories Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 4: Operating Manual Pnoz M Es Powerlink

    Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ m ES Powerlink. It is valid until new doc- umentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 5 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 6: Overview

    128 virtual inputs and outputs on the control system PNOZmulti can be defined in the PNOZmulti Configurator for communication with the fieldbus Ethernet POWERLINK. Max. 1 PNOZ m ES Powerlink can be connected to the base unit For details of the PNOZmulti 2 base units that can be connected, please refer to the document "PNOZmulti System Expansion".
  • Page 7: Front View

    Overview Front view Legend: X1, X2: Ethernet POWERLINK interfaces 0 V, 24 V: Supply connections : Functional earth LED: – Power – L/A1 – L/A2 – S/E (Status/Error) Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 8: Safety

    PNOZmulti 2. It is used for communication between the configurable control system PNOZmulti 2 and Ethernet POWERLINK. Ethernet POWERLINK is designed for fast data exchange at field level. The expansion module PNOZ m ES Powerlink is a pass- ive subscriber (Controlled Node) of the Ethernet POWERLINK. The basic communication functions with Ethernet POWERLINK conform to the System Description published by the POWERLINK User Group (EPSG).
  • Page 9: Safety Regulations

    Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 10: Function Description

    LINK are selected and configured in the PNOZmulti Configurator. The base unit and the fieldbus module PNOZ m ES Powerlink are connected via a jumper. After the supply voltage is switched on or the PNOZmulti control system is reset, the fieldbus module PNOZ m ES Powerlink is configured and started automatically.
  • Page 11: Block Diagram

    Function description Block diagram 24 V Ethernet Module Supply POWERLINK Data (ST) Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 12: Installation

    Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm 22,5 101,4 (4,11“) (0,88“) Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 13: Connect The Base Unit And Expansion Modules

    Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 14: Commissioning

    The power supply must meet the regulations for extra low voltages with protective sep- aration. CAUTION! Only connect and disconnect the expansion module when the supply voltage is switched off. NOTICE When installing, you must refer to the guidelines of the Ethernet POWER- LINKUser Group. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 15: Connecting The Supply Voltage

    PNOZmulti Configurator. Proceed as described in the operat- ing instructions for the base unit. NOTICE For the commissioning and after every program change, you must check whether the safety devices are functioning correctly. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 16: Connection Example

    Commissioning Connection example Ethernet POWERLINK Managing Node Ethernet POWERLINK Ethernet POWERLINK Ethernet POWERLINK Slave 1 Slave 2 Slave 3 Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 17: Operation

    When the supply voltage is switched on, the PNOZmulti safety system copies the configur- ation from the chip card. The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base unit. The expansion module PNOZ m ES Powerlink is configured and started automatically. Messages Legend LED on...
  • Page 18 The bus controller is in a PRE_OPERATIONAL_2 state. short Green: 3 x The bus controller is in a READY_TO_OPERATE state. short Green The bus controller is in an OPERATIONAL state. Green The bus controller is in a STOPPED state. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 19: Technical Details

    EN 60068-2-1/-2 Temperature range -25 - 70 °C Climatic suitability In accordance with the standard EN 60068-2-30, EN 60068-2-78 Condensation during operation Not permitted Max. operating height above sea level 2000 m EN 61131-2 Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 20 0,5 Nm Conductor cross section with spring-loaded terminals: Flexible with/without crimp connector 0,2 - 2,5 mm², 24 - 12 AWG Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 21 Technical Details Mechanical data Dimensions Height 101,4 mm Width 22,5 mm Depth 110,4 mm Weight 90 g Where standards are undated, the 2013-10 latest editions shall apply. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 22: Order Reference

    Spring-loaded terminals, 10 pieces 783 543 PNOZ mmcxp 10 pcs. Screw terminals Screw terminals, 1 piece 793 542 PNOZ mmcxp 1 pc. Screw terminals Screw terminals, 10 pieces 793 543 PNOZ mmcxp 10 pcs. Operating Manual PNOZ m ES Powerlink 1003193-EN-05...
  • Page 23 Back cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...

Table of Contents