ZK300DC SWING GATE OPERATOR USER'S MANUAL

10. Electrical / Setting

Learn remote controls

Adding extra remote controls (Learn):
Press the Learn Button on the control board for 1 second, release the button, the
indicator 'LED' will be on.
Press the same button you want to use twice, the 'LED' will flash 6 times, the learning
process is completed.
Up to 40 remote controls may be used.

To erase all remote controls

Press and hold the Learn Button on the control board for 8 seconds until 'LED' turns
off. This indicates that all the remote controls have been erased completely.
The remote control mode (single or three channel mode) is adjustable by Jumper cap,
put the jumper cap on left two pins, with single channel mode, put the jumper cap on
right two pins, the remote control is three channel mode.
Warning: DO NOT operate the gate operator unless the gates are in full view and free
from objects such as cars and children/people.
For safety and security, we recommend that the factory setting be replaced with a
personal code.
Setting open and close limit position
Press and hold K1 button for 3 seconds, '11' will be displayed on the LED.
While '11' is displaying on LED, Press K2 and K4 button to set open limit for gate B,
press K1 button to confirm the setting. The gate B will then close automatically to its
closed position.
Then '22' will be displayed on LED. press K2 and K4 button to set open limit for gate
A, press K1 button to confirm the setting, the gate A will then close automatically to
its closed position.

Setting Auto close time

Press and hold K2 button for more than 4 seconds, release the button until '-' is
displayed on LED
Press K2 button to increase auto-close time, press K4 button to decrease auto-close
time. The auto-close delay time: 0–90 seconds.
Setting Interval time between two gates (Default: 2 seconds)
Press and hold K4 button for more than 4 seconds, release the button until 'H' is
displayed on LED.
Press K2 button, 'H' is indicated on the LED display, without interval time, press K4
button, 'Ⅱ' is indicated on the LED display, the interval time between two gates is 2
seconds.
Setting obstruction force (level1- level20 adjustable)
ZK300DC will stop if it encounters an obstruction during closing or opening.
Press and hold K3 button for more than 4 seconds, until the number '-' is displayed
on LED.
Press K2 to increase the obstruction force, the maximum force is level 20. Press K4
to decrease force, the minimum force is level 1.
Press K1 to confirm the setting. 'II' is indicated on the LED display.