Xs1, Shield Connection; Ground Connection Of Housing - Bosch Rexroth IndraDrive C HCS03.1 Planning Manual

Drive controllers
Table of Contents

Advertisement

Rexroth IndraDrive C HCS03.1

XS1, Shield Connection

Ground Connection of Housing

DOK-INDRV*-HCS03.1****-PR02-EN-P
Fig. 6-41:
Shield connection XS1
Connection for the shields of lines connected to the control section.
Note:
Always connect shields of control lines with a large metal-to-
metal contact surface.
The ground connection of the housing is used to provide functional safety
of the drive controllers and protection against contact in conjunction with
the equipment grounding conductor.
Ground the housings of the drive controllers:
1. Connect the bare metal back panel of the drive controller in
conductive form to the mounting surface in the control cabinet. To do
this use the supplied mounting screws.
2. Connect the mounting surface of the control cabinet in conductive
form to the equipment grounding system.
See also Project Planning Manual of drive system, chapter "System
Connections of the Components"
6-25
Electrical Data
ANHC0002EN00.FH9