Eldat Easywave RCR02E5002A01 Manual

Din rail receiver

Advertisement

Quick Links

DIN Rail receiver RCR02
EN
Models
RCR02E5002A01
Technical Data
Frequency:
868.30 MHz
Modulation:
FSK
Coding:
Easywave
Power supply:
230 V AC 50 Hz
Output:
2 potential-free relay
contacts 16 A
(normally open)
Power consumption:
0.6 W standby
Connected load:
see Load Table
Operating temperature: -20 °C to +60 °C
Dimensions (W/L/H):
34.5 /89.6/62.8 mm
Weight:
108 g
Load Table
Load type
Ohmic load:
Incandescent lamps, 230 V
halogen lamps etc.
IInductive load:
Halogen lamps with wound
transformers (transformer at
least 85% loaded)
Non- or serial-compensated
fluorescent lamps with ferro-
magnetic ballasts
Parallel-compensated fluores-
cent lamps with ferromagnetic
ballasts
Electronic ballast capacity:
electronic ballasts, electronic
transformers, etc.
Function
The RCR02E 2TE DIN rail receiver is used for the
potential-free activation of two mains-powered
devices.
The receiver can be operated in ON/OFF, PULSE
and DEAD MAN'S SWITCH modes. The ON/OFF
mode can also be used with two TIMER functions
and a LOGIC function.
Scope of Delivery
DIN Rail receiver RCR02 2TE,
operating manual
2TE
RCR02E5004A01
Technical Data
Frequency:
Modulation:
Coding:
Power supply:
Output:
Power consumption:
Connected load:
Operating temperature: -20 °C to +60 °C
Dimensions (W/L/H):
Weight:
Load Table
max. load
Load type
16 A / 3,680 VA
Ohmic load:
Incandescent lamps, 230 V
halogen lamps etc.
3 A / 690 VA
IInductive load:
Halogen lamps with wound
transformers (transformer at
least 85% loaded)
3 A / 690 VA
Non- or serial-compensated
fluorescent lamps with ferro-
magnetic ballasts
3 A / 720 VA
Parallel-compensated fluores-
cent lamps with ferromagnetic
ballasts
4 A / 920 VA
Electronic ballast capacity:
electronic ballasts, electronic
transformers, etc.
Function
The RCR02E 4TE DIN rail receiver is used for the
potential-free activation of four mains-powered
devices.
The receiver can be operated in ON/OFF, PULSE
and DEAD MAN'S SWITCH modes. The ON/OFF
mode can also be used with two TIMER functions
and a LOGIC function.
Scope of Delivery
DIN Rail receiver RCR02 4TE,
operating manual
Intended Use
The device is intended for mounting on a DIN rail
in a distribution box or a control cabinet in dry
rooms. The unit may only be used as a wireless
receiver for activating electrical devices in accord-
ance with the load table. To be operated with Ea-
sywave wireless transmitters.
The manufacturer shall not be liable for any dam-
age caused by improper or non-intended use.
Safety Advice
Caution! Electrical installation must only be
carried out by a qualified electrician, failure
to do so may result in fire or electric shock.
4TE
Observe the applicable laws, standards and re-
gulations as well as the operating instructions of
the appliances to be switched!
868.30 MHz
This device is only intended for indoor use in
FSK
dry and dust-free rooms.
Easywave
Have faulty devices checked by the manufac-
230 V AC 50 Hz
turer!
2 potential-free relay
Do not make any modifications to the device!
contacts 16 A
(normally open)

Setting up the Receiver

2 potential-free relay
contacts 16 A
(change-over)
0.6 W standby
see Load Table
70.5 /89.6/62.8 mm
186 g
max. load
16 A / 3,680 VA
3 A / 690 VA
A
A1
The device is intended for installation on a stand-
3 A / 690 VA
ard DIN rail (35 x 7.5 mm). Pull out the slide to
allow fixing through mounting points.
Only a qualified electrician may install, connect
NO
in accordance with the connection diagram and
set up the receiver.
3 A / 720 VA
Please note the „5 safety rules" for electri-
NC
cians!
1.5 A / 345 VA
1. Switch off the power supply. Follow the „5
4 A / 920 VA
2. Mount the RCR02 onto the rail.
3. Connect the cables for the power supply and
4. Switch on the supply voltage. Follow the „5
5. Programme the receiver according to the op-
In unfavourable environmental conditions, the ex-
ternal antenna ACC-ANT50-03-21P can be used
to improve wireless reception. This is not included
in the delivery and can be ordered separately.
Before installing the device, carefully
read through this operating manual!
Installing the Receiver .............................. 1
Mounting the Receiver ....................... 1
Electrical Connection ......................... 2
Operation ................................................... 2
Operating Modes ............................... 3
Programming ............................................ 5
Setting the TIMER...............................5
Deleting the Transmitter ..................... 6
Reset ................................................. 6
General Information .................................. 8
Installing the Receiver
Mounting the Receiver
safety rules"!
for the devices in accordance with the con-
nection diagram (see page 2).
safety rules"!
erating manual (see pages 4-5).
1

Advertisement

Table of Contents
loading

Summary of Contents for Eldat Easywave RCR02E5002A01

  • Page 1: Table Of Contents

    DIN Rail receiver RCR02 Models Intended Use The device is intended for mounting on a DIN rail in a distribution box or a control cabinet in dry rooms. The unit may only be used as a wireless receiver for activating electrical devices in accord- ance with the load table.
  • Page 2: A2 Electrical Connection

    Installing the Receiver Electrical Connection Connection external Connection external antenna Connection external antenna antenna: ACC-ANT50-03-21P ACC-ANT50-03-21P Connect the black anten- na cable to the antenna terminal and the white cable to the functional earth termi- Note: Mount the an- tenna away from metal housing.
  • Page 3: B2 Operating Modes

    Operation Operating Modes Press the P button to specify whether you want to In 2-button operation (2TB), switching ON trans- In 1-button operation (1TB), each button switches programme a transmitter in 2-button operation or mitter buttons A or C starts or retriggers the TI- ON and OFF alternately or triggers a PULSE.
  • Page 4: B3 Conversion Table For Timer

    Operation Conversion table of TIMER II Conversion seconds with multiplier in time (Hr: min: sec) Multiplier Multiplier Seconds Counter 1000 Seconds Counter 1000 0:00:01 0:00:10 0:01:40 0:16:40 0:00:31 0:05:10 0:51:40 8:36:40 0:00:02 0:00:20 0:03:20 0:33:20 0:00:32 0:05:20 0:53:20 8:53:20 0:00:03 0:00:30 0:05:00 0:50:00...
  • Page 5: C Programming

    Programming Programming the Transmitter Operation Display Note If a previously programmed transmitter is pro- [Press the button] grammed again in the same output, the previous  operating mode is P 1x briefly LED 2TB flashes Programming mode 2-button operation started. overwritten with the new operating mode.
  • Page 6: C3 Deleting The Transmitter

    Programming Deleting the Transmitter Operation Display Note In delete mode, individual transmitters can be de- [ P r e s s b u t t o n ] leted from the memory of an output.  1x briefly or LED 2TB flashes Programming mode started.
  • Page 7: D General Information

    Any unauthorised tampering with, or modifica- tions to, the product shall render this warranty null and void. Conformity ELDAT GmbH hereby declares that the radio equipment type RCR02 is in compliance with the Directive 2014/53/EU. The full text of the EU declaration of conformity can be obtained at the following internet address: www.eldat.de...
  • Page 8 ELDAT GmbH Im Gewerbepark 14 15711 Königs Wusterhausen Germany Phone: + 49 (0) 33 75 / 90 37-310 Fax: + 49 (0) 33 75 / 90 37-90 Internet: www.eldat.de E-Mail: info@eldat.de...

This manual is also suitable for:

Easywave rcr02e5004a01Easywave rcr02 series

Table of Contents