Table of contents About this document ................Applicable documents ................Technical terms ..................Revision history ..................Mounting ....................Installation position and space requirements ........... Dimensions....................Mounting on a level surface ..............Connecting the pipe system ..............Mounting the ASD filter box..............Removing the housing cover..............
1.2 Technical terms Term Explanation Aspirating smoke detector ASD Connect Siemens software FDnet/C-NET Addressed detector line General purpose input; connection for an external switch Normally closed; standard state of connection is closed Normally open; standard state of connection is open...
Mounting Installation position and space requirements 2 Mounting 2.1 Installation position and space requirements Requirements for the installation location ● Only to be mounted within a building where the ambient conditions are permissible ● No direct sunlight ● Minimal dust load ●...
Mounting Mounting on a level surface 2.3 Mounting on a level surface Installation location: level surface Four screws are to hand. 8...10 5...6 Housing cover has been removed. See 'Removing the housing cover [➙ 13]'. 1. Drill four holes using the supplied drilling template. For the hole pattern, see 'Dimensions [➙ 8]'.
Mounting Connecting the pipe system 2.4 Connecting the pipe system >500 Fig. 5: Connecting the pipe system (example) The pipe system has been mounted. There is a straight pipe at least 500 mm in length leaving the aspirating smoke detector. 1. Press the pipe (1) into the air inlet (without adhesive). 2.
Mounting Mounting the ASD filter box 2.5 Mounting the ASD filter box ◈ Install the ASD filter box FDAZ292 into the pipework system with a clearance of at least 100 mm to the aspirating smoke detector. You will find more information on mounting the ASD filter box in document A6V10877841.
Mounting Removing the housing cover 2.6 Removing the housing cover NOTICE Electrostatic discharge Damage to electronic components ● Ground yourself before opening the housing: Wear a grounding strap or touch a ground point. Open the housing to access the service area: 1.
Mounting Rotating the front indicator 2.7 Rotating the front indicator Housing cover has been removed. See 'Removing the housing cover [➙ 13]'. 1. Disconnect the power supply DC 24 V: pull the connector out. 2. Remove the four screws. 3. Lift the front indicator straight up. 4.
Page 15
Mounting Rotating the front indicator 6. Install the front indicator. – Carefully insert the 14-pin connector. 7. Tighten the four screws. The front indicator is now installed rotated by 180°. 8. Plug in the DC 24 V connector. A6V11783970_en--_a 15 | 26...
Mounting Folding the carrier up 2.8 Folding the carrier up Housing cover has been removed. See 'Removing the housing cover [➙ 13]'. 1. Remove the three screws (1). 2. Pull the aspirator connector (2) out. 3. Rotate the carrier in the direction of the arrow. The carrier has been rotated by 90°.
Mounting Replacing the detection chambers 2.9 Replacing the detection chambers The carrier has been folded up. See 'Folding the carrier up [➙ 16]'. The carrier is not depicted in the figures below to give a clearer view of the parts concerned. 1.
Mounting Replacing the aspirator 2.10 Replacing the aspirator Housing cover has been removed. See 'Removing the housing cover [➙ 13]'. 1. Pull the aspirator holder out. 2. Unplug the cable from the aspirator and the carrier. 3. Remove the aspirator from the Y pipe. 4.
Page 19
Mounting Installing an extension card – Align the 14-pin connector with the socket. 3. Carefully insert the 14-pin connector. 4. Push the extension card on as far as it will go. The snap fasteners latch into place. The extension card is now installed. 5.
Installation 3 Installation CAUTION Electrical voltage Electric shock ● Disconnect all lines from the power supply before starting any installation work. Fig. 8: Overview of connections Slot I, extension card GPI inputs Slot II, extension card Relay outputs Power supply DC 24 V FDnet/C-NET detector line Housing cover has been removed.
Installation Power supply DC 24 V 3.1 Power supply DC 24 V ◈ Connect the cable to the connector. – Cable cross section: 0.2…2.5 mm flexible (AWG 12…30) – Cable cross section: 0.2…1.5 mm rigid +24 V Fig. 9: Connecting the power supply DC 24 V 3.2 GPI inputs Configurable inputs for external switches.
Installation Relay outputs 3.3 Relay outputs Configurable outputs for issuing signals or controlling external devices such as the blowing-out unit. 1. Connect the cable to the connector. – Cable cross section: 0.2…1.5 mm flexible/rigid 2. Connect a monitoring resistor (1) for each relay output as required. Fault Fig.
Installation 4...20 mA outputs (optional) 2. Connect the cable to the connector. – Cable cross section: 0.2…1.5 mm flexible/rigid 3. Connect a monitoring resistor (1) for each relay output as required. Fig. 13: Connecting relay outputs 3.6 4...20 mA outputs (optional) The 4…20 mA outputs are located on the extension card FDAZ296. See '4...20mA card FDAZ296'.
Index Index ASD Connect ............. 6 ASD filter box FDAZ292 ........12 Front indicator ..........14 Installation Installation position ......... 7 Requirements ..........7 Space requirements ........7 Intended use ............5 List of compatibility .......... 5 Portal ..............6 Return pipe ............