Main Inverter Status - SolarEdge SE12.5K Installation Manual

Three phase inverter with synergy technology
Hide thumbs Also See for SE12.5K:
Table of Contents

Advertisement

50
Viewing System Status

Main Inverter Status

Power
100 kW
   P_OK: 138 of
141
Optimizers
Connected
Status
Production
CosPhi
1.00
Voltage
850 Vdc
Switch Off. Production disabled
Commissioning
Inverter: The inverter serial number
Power: The AC output power
Voltage (Vac): The AC output voltage
Frequency: The AC output frequency
P_OK: xxx of yyy: There is a connection to the power optimizers and at least
one power optimizer is sending monitoring data. XXX is the number of power
optimizers for which telemetries have been received in the last two hours.
YYY is the number of paired power optimizers identified during the most
recent pairing process. If XXX and YYY are not equal, there may be a
problem in one or more power optimizers.
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.2
Status
Inverter
SN 07318000C
Voltage
Frequency
277 Vac
60.9 Hz
Server Comm.
S_OK
(LAN)
 Switch
OFF
Limit
Country
No Limit
Netherlands
Temp
Fan
20 C
OK
       ›

Advertisement

Table of Contents
loading

Table of Contents