PM motor
For the PM motor, see the cable sizing table below. This table is
given for reference only, and it must under no circumstances be
used instead of the current local standards.
Product
Power drive model
number
96943883
FC-202P45K IP55 380-480 V
96943884
FC-202P55K IP55 380-480 V
96943885
FC-202P75K IP55 380-480 V
96943886
FC-202P90K IP55 380-480 V
99292227
FC202P110K IP54 380-480 V
99292229
FC202P160K IP54 380-480 V
99292229
FC202P160K IP54 380-480 V
99292230
FC202P200K IP54 380-480 V
P
:Nominal power.
n
I
: Nominal current.
n
I
M:Maximum continuous line current permitted in motor mode
L
(power drawn by the motor).
(1)
The value of the rated current and the motor cable cross-
sections are given for reference only. As a reminder, the motor
rated current permitted varies according to the switching
frequency and the temperature.
(2)
For 110 kW and higher power, there are two wires on each
phase, so six wires are used in total.
(3)
170M: Bussmann fuses.
(4)
The power cable cross-sections are given for reference only
for a current corresponding to the value of the Ico current at 3
kHz, a maximum length of 50 m, output frequency less than
100 Hz and an ambient temperature of 40 °C. We recommend
screened multi-core power cables. See fig. 20. The values
supplied are typical values.
Fig. 20 Screened multi-core cable
(5)
The PE conductor cross-section must be not less than half of
the associated phase conductor cross-section assuming that
the same material is used.
AC motor
For BMS systems supplied with AC motor, see recommendations
from VFD manufacturer.
Software
The Grundfos BMS hs pump is supplied with the required
software configuration file, if the VFD is supplied by Grundfos.
You can find the number of the software configuration file on the
small sticker placed below the control panel in the control cabinet
for the frequency converter.
See also the configuration reference guide supplied with the
product.
Do not change any settings without guidance from
Grundfos Service.
10
Mains supply
I
M
L
P
[A]
n
[kW]
380-440 V 440-480 V
45
90
80
55
106
105
75
146
130
90
177
160
110
204
183
160
304
291
160
304
291
200
381
348
3.4.2 BMS hp pump
See the quick guide or installation and operating instructions
supplied with the product.
See the nameplate to identify the motor type and type of control
board.
Default settings for BMS hp motor:
minimum speed: 1700 rpm
maximum speed: 3600 rpm
setpoint input: 4-20 mA
relay: alarm.
3.4.3 BMST system
For electrical installation, see section
3.4.4 BMSX system
For electrical installation, see sections
3.4.2 BMS hp
Cable cross
Recommended
section
(3)
fuse
2
(2)(5)
[mm
]
gG-100
3 x 50 + PE
gG-160
3 x 50 + PE
aR-200
3 x 150 + PE
aR-250
3 x 150 + PE
170M2620
6 x 95 + PE
170M4015
6 x 95 + PE
170M4015
6 x 95 + PE
170M4016
6 x 185+ PE
If not controlled by a 4-20 mA signal, the external
setpoint input must be disabled by the remote
control.
pump.
(1)
Motor
Cable cross
P
I
n
n
section
[kW]
[A]
2
(2)(4)(5)
[mm
]
44
84.5
3 x 50 + PE
52
97.5
3 x 50 + PE
70
127.0 3 x 150 + PE
85
156.0 3 x 150 + PE
100
183.0
6 x 95 + PE
140
264.0
6 x 95 + PE
160
316.0
6 x 95 + PE
180
363.0 6 x 185 + PE