6.2.4 Connection to room thermostats (on/off)

Connect up the high temperature system room thermostat to
terminals 9. and 10 ("Figure 11").
The thermostat for the low temperature system must instead be
connected to terminals n. 11 and 12 ("Figure 11")..

6.2.5 Connection to weather temperature probe

If you want to use a weather thermoregulator, the external
probe (optional) must be connected up to terminals n.7 and 8 ().
The external probe must be placed on an outer wall facing north
to north-east at a height of at least 2.5 metres and at a distance
from windows, doors and air vents.
Protect the probe from direct exposure to the sun. Contact the
Technical Assistance Service authorized by
to be adjusted or the weather function excluded.
Correspondence table for all sensors
Measured temperatures (°C) - Resistive values of the sensors (Ω).
T (°C)
R (Ω)
T (°C)
R (Ω)
-20
67739
13
15912
-19
64571
14
15289
-18
61568
15
14694
-17
58719
16
14126
-16
56016
17
13582
-15
53452
18
13062
-14
51018
19
12565
-13
48707
20
12090
-12
46513
21
11634
-11
44429
22
11199
-10
42449
23
10781
-9
40568
24
10382
-8
38780
25
9999
-7
37079
26
9633
-6
35463
27
9281
-5
33925
28
8945
-4
32461
29
8622
-3
31069
30
8313
-2
29743
31
8016
-1
28481
32
7731
0
27279
33
7458
1
26135
34
7196
2
25044
35
6944
3
24004
36
6702
4
23014
37
6470
5
22069
38
6247
6
21168
39
6033
7
20309
40
5828
8
19489
41
5630
9
18706
42
5440
10
17959
43
5258
11
17245
44
5082
12
16563
45
4913

6.2.6 Frost protection

The heating unit electronic control includes a frost protection
function. When the flow temperature sinks to below a minimum
value, the burners start working at minimum power according
to the procedure used to set the functional parameters.
The frost protection mode is activated even if the external probe
(supplied with the appliance) is not connected to the boiler: pa-
rameters 14 (related to the Ch1 high temperature system) and 22
(Ch2 low temperature system) are in fact in default and set in
weather function.
Should one not want to connect the probe, the boiler must be
made to work at a fixed point to avoid problems. The parameter
14 and 22 settings may only be altered by a Technical Assistance
Service authorized by
R
.
R
if the curve has
T (°C)
R (Ω)
T (°C)
R (Ω)
46
4751
79
1717
47
4595
80
1669
48
4444
81
1622
49
4300
82
1577
50
4161
83
1534
51
4026
84
1491
52
3897
85
1451
53
3773
86
1411
54
3653
87
1373
55
3538
88
1336
56
3426
89
1300
57
3319
90
1266
58
3216
91
1232
59
3116
92
1199
60
3021
93
1168
61
2928
94
1137
62
2839
95
1108
63
2753
96
1079
64
2669
97
1051
65
2589
98
1024
66
2512
99
998
67
2437
100
973
68
2365
101
948
69
2296
102
925
70
2229
103
901
71
2164
104
879
72
2101
105
857
73
2040
106
836
74
1982
107
815
75
1925
108
796
76
1870
109
776
77
1817
110
757
78
1766
9
Power and fuel gas supply must be activated and the water
system at a correct pressure for the frost protection system
to function.
9
QGlycol can be used as an additive for the system (up to a
maximum of 50%) there where considered necessary by the
person responsible for the project, keeping in mind that this
substantially reduces efficiency as it alters the specific heat
of the fluid. Furthermore several parts of the system could
be damaged by altering the pH.
6.2.7 Connection to 0-10v external
thermoregulator
An external thermoregulator connection using a 0 – 10 v signal
could be used by connecting the output signal to terminals n.13
and 14 ("Figure 11").
9
The positive pole of the signal output must be connected to
terminal 13 for the device to work correctly.

6.2.8 Connection to alarm device

A beeping or visual alarm device, to signal any technical faults,
may be connected outside by a special output with clean con-
tact on the boiler terminal board.
The alarm device must be connected to terminals n.18 and 19
("Figure 11").

6.2.9 Remote control

If the remote control is to be used, it must be connected to ter-
minals no. 15, 16 and 17 ("Figure 11").

6.3 Emergency mode

The Condexa Pro2 EVO electronic control system includes a func-
tional mode called "Emergency", which can be activated in case
of a Master board malfunction.
The master board can in fact be excluded so as to enable the
system to work with a flow temperature preset in default by the
manufacturer, guaranteeing the heating unit with continual
service.
9
Qualified personnel only may work on the electrical system
and in compliance to provisions of the law, with particular
attention to rules on safety.
The following procedure must be adopted to enable the "Emer-
gency" function:
− Disconnect the 4-pole J14 connector from the master
board (see "Figure 12" );
− set all four J17 switches located on each Slave of the ther-
mal assembly on the Off position (see "Figure 13" );
− Supply power to all the circulators in the system direct-
ly from the mains using the specific relays/change-over
switches;
− Connect terminal X1 or terminal X2 (which are part of the
J14 connector wiring disconnected during the first step
of this procedure) to a 24 V ac power supply (see "Figure
15").