Particulate contamination
Conductive dust
Corrosive dust
Table 23. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Specifications
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-
data center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point
less than 60% relative humidity.
NOTE:
This condition applies to data center and non-
data center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Technical specifications