Helios EVS Series Installation And Operating Instructions Manual page 52

Smoke exhaust fan control system for mechanical smoke extraction systems
Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Instructions
EN
EVS-W
Wiring diagram - EVS-W
Note: Valid for the connection of smoke extraction fans with PTC thermistor (KL)
Fuse and cable see
table in MBV
-W1
+24VDC
24
br
DL plug
Lamp test
ye
14 pol.
EVS-ST3.2
Fireman's switch
-
Signals
1
2
3
4
5
6
10kW
1
1
2
3
6 7
8 9
ye gn rd
1
2
3
6
7 8
2
10kW
1
2
3
6 7
8 9
ye gn rd
max. no.: 6
Ref.no.: 08255-004
Fireman's switch
FWS2
4x2x0,8mm
(shielded)
-W4
Smoke exhaust fan control system – EVS
2
4
6
Isol. switch
RS 3+1...
1
3
5
Fan 1
cable
see table in MBV
-W2
25 26
Y
Stage 1:
U = 0-5V
Stage 2:
U = 5-10V
Smk extr.:
U = Stage 2 / 10V
OnBoard diagnosis
I
max. 10mA
Y
10V
Stage 2
Stage 1
Stage 2
BMZ autoRST
ON
BMZ
Ventilation funct.
24VDC
+ -
-
8 9
10 11
12 13
17 18
7
1
2,7kW
BMZ
rd
9
3
2,7kW
4
BMZ
2
1
3
rd
WSUP
BMZ
-
-
2x2x0,8mm
2x2x0,8mm
(shielded)
(shielded)
-W5
-W6
triggered
shown
60 61
50 51 52
53 54 55
+
System
reset
Smoke extr.
Fault
Signal
Signal
Press button:
pot.-free
pot.-free
direct : DKM, BMZ
max. contact load
> 1sec: RMR
> 3sec: FWS
230V AC / 2A
Button
Switch
Smoke detector
Pushbutton alarm
-
-
19
20
15
16
21
22 23
1
10kW
10kW
1
-
+
-
1
2
3 4 5
6
7
gn
ye
rd
Ein
Prev. detector
Previous detector
-
+
-
1
3 4 5
6
2
10kW
10kW
2
-
+
-
1
2
3 4 5
6
7
rd
gn
ye
max. no.: 60
max. no.: 20
Ref.no.: 04984-005
Ref.no.: 04985-003
Smoke detector
Pushbutton alarm (button)
DKM
RMR
2x2x0,8mm
4x2x0,8mm
(shielded)
(shielded)
-W7
-W8
20
2x2x0,8mm
31
32
27 28
Motor prot.
Control system
230VAC
Reset
MT 2A
24V/15VA
F2
-
N
MT 0,4A
Return signal
isolator switch
14
40 41 42 N
29
30
1
PE
8
8
Remove resistor or jumper if unit or detector
1
connected.
Insert resistor 10kW at last or only detector in
2
circuit.
8
Insert resistor 2,7kW at last or only detector in
3
circuit.
Ventilation only through smoke extraction fans
4
with ventilation function
Rep.
Cable function-maintaining
The specified cable types and dimensions are
minimum requirements without taking installation
type, cable length, network type and necessary
Isol. switch
function maintenance into account. The decisions
RS 3+1...
regarding the building must be made independently
2x2x0,8mm
(shielded)
by the executing installer.
-W9
Vers: 25.10.2017
Issue: 006
L
N
45
46
L
N
St.1
St.2
F1
Rel..
ventil.
Smoke extr.
Rel..
ventil.
L
N
43 44
PE
PE
Z A N
PE
M
1~
Smoke exhaust
Return signal
damper
damper "open"
5x1,5mm²
3x1,5mm²
-W10
-W11