Helios EVS Series Installation And Operating Instructions Manual page 43

Smoke exhaust fan control system for mechanical smoke extraction systems
Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Instructions
EVS-SD
Wiring diagram - EVS-SD
Note: Valid for the connection of smoke extraction fans without PTC thermistor (KL) or thermal contact (TK)
Isol. switch
RS 6+1...
Fuse and cable see
table in MBV
-W1
+24VDC
24
Lamp test
ye
br
DL plug
14 pol.
OnBoard Diagnosis
EVS-ST3.2
Fireman's switch
-
Signals
1
2
3
4
5
6
7
10kW
1
1
2
3
6 7
8 9
BMZ
ye gn rd
rd
1
2
3
6
7 8
9
2
10kW
1
2
3
6 7
8 9
BMZ
ye gn rd
rd
max. no.: 6
Ref.no.: 08255-004
BMZ
Fireman's switch
-
FWS2
4x2x0,8mm
2x2x0,8mm
(shielded)
-W4
-W5
Smoke exhaust fan control system – EVS
2
4
6
8
10
1
3
5
7
9
Fan 1
cable
see table in MBV
-W2
-W3
25 26
Y
Stage 1:
U = 0-5V
Stage 2:
U = 5-10V
Smk extr.:
U = Stage 2 / 10V
I
max. 10mA
Y
10V
Stage 2
Stage 1
Stage 2
BMZ autoRST
ON
BMZ
Ventilation funct.
24VDC
Smoke detector
+ -
-
10 11
12 13
8 9
17 18
22
1
2,7kW
-
+
Prev. detector
-
+
3
2,7kW
-
+
4
2
1
3
max. no.: 60
Ref.no.: 04984-005
WSUP
Smoke detector
-
RMR
2x2x0,8mm
2x2x0,8mm
(shielded)
(shielded)
-W6
-W7
12
11
triggered
shown
60 61
50 51 52
53 54 55
+
System
reset
Smoke extr.
Fault
Signal
Signal
Press button:
pot.-free
pot.-free
direct : DKM, BMZ
> 1sec: RMR
max. contact load
> 3sec: FWS
230V AC / 2A
Button
Switch
Pushbutton alarm
-
-
23
19
20
15
16
21
14
1
10kW
10kW
1
-
1
2
3 4 5
6
7
8
rd
gn
ye
Ein
Previous detector
-
1
3 4 5
6
8
2
10kW
10kW
2
-
1
2
3 4 5
6
7
8
rd
gn
ye
max. no.: 20
Ref.no.: 04985-003
Pushbutton alarm (button)
DKM
4x2x0,8mm
(shielded)
(shielded)
-W8
11
27 28
31
32
Motor prot.
Control system
230VAC
F1
Reset
Rel.
MT 2A
ventil.
24V/15VA
F2
-
N
MT 0,4A
Return signal
L
isolator switch
40 41 42 N
29
30
1
PE
Z A N
M
1~
Smoke exhaust
damper
5x1,5mm²
-W10
Remove resistor or jumper if unit or detector
1
connected.
Insert resistor 10kW at last or only detector in
2
circuit.
Insert resistor 2,7kW at last or only detector in
3
circuit.
Ventilation only through smoke extraction fans with
4
ventilation function
Rep.
Cable function-maintaining
The specified cable types and dimensions are
minimum requirements without taking installation
Isol. switch
type, cable length, network type and necessary
function maintenance into account. The decisions
RS 6+1...
regarding the building must be made independently
2x2x0,8mm
(shielded)
by the executing installer.
-W9
EN
Vers: 25.10.2017
Issue: 007
L
N
45
46
L
N
St.1
St.2
Smoke extr.
Rel.
ventil.
N
43 44
PE
PE
PE
Return signal
damper "open"
3x1,5mm²
-W11