Siemens Microinverter Installation

Follow the instructions in this section to install Siemens SMIINV215R60XX Microinverters.
DANGER
Power before working on this equipment. Be aware that installation of this
equipment includes risk of electric shock. Normally grounded conductors may
be ungrounded and energized when a ground fault is indicated.
WARNING: Before installing the Siemens Microinverter, read all instructions
and cautionary markings in the user manual, on the Siemens Microinverter, and
on the photovoltaic array.
WARNING: Perform all electrical installations in accordance with all local
electrical codes and the NEC
WARNING: Connect the Siemens Microinverter to the electrical utility grid only
after receiving prior approval from the utility company.
WARNING: Be aware that only qualified personnel should connect the Siemens
Microinverter to the electrical utility grid.

Compatibility and Capacity

The Siemens SMIINV215R60XX Microinverters are electrically compatible with most 60-cell PV
modules. For more information, see Technical Data page 25 of this manual.
Refer to the Siemens website (http://www.usa.siemens.com/microsolar) for a list of electrically-
compatible PV modules and approved PV module racking systems. To ensure mechanical
compatibility, be sure to order the correct connector type for both microinverter and PV module
from your distributor.
Electrical Compatibility
Model Number
SMIINV215R60MC
SMIINV215R60TY
Voltage and Capacity
Maximum number of SMIINV215R60XXs per 20 amp AC Branch Circuit
Service type
Single phase 240 V or 208 V
Three phase 208 V
Page 7
Hazardous voltage. Will cause death or serious injury. Turn off
R
, ANSI/NFPA 70.
Works with PV Module Type
60 cell
60 cell
Max SMIINV215R60XXs
per branch
Copyright 2011 Siemens Industry, Inc.
Module Connector Type
MC-4 Type 2 Locking or
Tyco Solarlock Locking
Max PV modules per branch
17
25
Amphenol H4 Locking
17
25