4.20 Parameters: 30-** Special Features

30-20 High Starting Torque Time [s]
Range:
Function:
Size related
[0 - 60 s] High starting torque time for PM
*
motors in VVC
feedback.
30-21 High Starting Torque Current [%]
Range:
Function:
Size related
[ 0 - 200.0 %] High starting torque time for PM
*
motors in VVC
feedback.
30-22 Locked Rotor Protection
Option:
Function:
[0]
Off
*
[1]
On
The locked rotor protection for PM motors.
30-23 Locked Rotor Detection Time [s]
Range:
Function:
0.10 s
[0.05 - 1 s] The locked rotor detection time for PM
*
motors.
30-83 Speed PID Proportional Gain
Range:
Size related
[0 - 1 ]
*
MG07C102
Programming Guide
+
mode without
+
mode without
Function:
Danfoss A/S © 12/2015 All rights reserved.