Troubleshooting - OGI TotalArc BMS 460346 SOLAR POWER Operator's Manual

Table of Contents

Advertisement

ISSUE
SIGNAL
Pilot Does Not
SOLID RED
Light
LIGHT
GREEN
FADING
LIGHT
No Flame/
SOLID RED
System
LIGHT
Unresponsive to
RESET
command

TROUBLESHOOTING

MEANING
LOCKOUT
System shuts down
CONDITION
and waits for Operator
LOCKOUT
Waits for purge period
CONDITION –
Purge timer waiting
accepting a manual
for next relight
reset or attempting
attempt.
LOCKOUT
System shuts down
CONDITION
and waits for Operator
11
REACTION
reset
to expire before
another relight.
reset.
POTENTIAL CAUSES
Improper positioning of
ignitor/flame rod to Pilot Head
(See figure 6 Page IV)
Poor ground between Relighter
Ignition Module (in flame
arrestor) and Pilot Head
Low Battery Voltage (11.50 Volt
minimum required)
Pilot ignition / sensing cable
connection
Poor termination of pilot ignition
/ sensing cable
Confirm electrical insulating
rubber boot is installed.
Confirm pilot gas valve has
power – check using a meter set
to DC voltage by putting the red
lead into terminal block TS1-13
and the black lead into terminal
block TS1-15.
Confirm gas pressure is
maintained even after pilot valve
opens
Confirm proper gas supply to
pilot gas valve.
Confirm safety input is active
Inspect heater safety chain
going into the TotalArc BMS for
failures.
Check for power using a meter
set to DC Voltage by putting the
red lead in terminal block TS1-8
and the black lead into TS1-2.