Troubleshooting - OGI TotalArc BMS 460246 SOLAR POWER Operator's Manual

Table of Contents

Advertisement

ISSUE
SIGNAL
Pilot
DOUBLE FLASH
Relighter
Lockout
SINGLE FLASH
No Pilot
FAST BLINK –
Flame Ignited
Right after
START/RELIGHT
BURNER push
button is pressed

TROUBLESHOOTING

MEANING
LOCKOUT - with
Two-minute burner
burner TCV
shutdown condition to
DISABLED
allow BASO to cool
down.
LOCKOUT - with
TotalArc main gas
burner TCV
valve released to
RELEASED: the
OPEN; BASO Pilot
system has
Guard should cool
maintained the main
down and close main
gas closed for a
gas valve
period of two-
minutes and has
now been released.
Ignition process
Spark present at
ignition rod
11
REACTION
POTENTIAL CAUSES
BASO Pilot Guard Valve or
Thermocouple issues.
Confirm BASO gas supply
and operation.
Improper positioning of
ignitor/flame rod to Pilot
Head (See figure 6 Page
IV)
Poor ground between
Relighter Ignition Module (in
flame arrestor) and Pilot
Head
Low Battery Voltage (11.50
Volt minimum required)
Pilot ignition / sensing cable
connection
Poor termination of pilot
ignition / sensing cable
Confirm electrical insulating
rubber boot is installed.
Confirm Spark Gap (See
Figure 6 Ignition Rod
Installation Page IV)
BASO Pilot Guard Valve or
Thermocouple issues.
Confirm BASO gas supply
and operation.
Improper positioning of
ignitor/flame rod to Pilot
Head (See figure 6 Page
IV)
Poor ground between
Relighter Ignition Module (in
flame arrestor) and Pilot
Head
Low Battery Voltage (11.50
Volt minimum required)
Pilot ignition / sensing cable
connection
Poor termination of pilot
ignition / sensing cable
Confirm electrical insulating
rubber boot is installed.