5. From the Connection Type pull-down menu, for this example choose
Multicast.
6. From the Configuration pull-down menu, for this example choose
Configuration signature must match.
7. In the Requested Packet Interval (RPI) box, enter 10 ms.
8. In the Connection Reaction Time Limit (CRTL), enter 40.1 ms.
9. Click Add.
This limits the packet size for normal communication. If detailed status is
required when a fault occurs, that data can be read explicitly via MSG
instructions.
10. Repeat steps
output connections.
Notice that the connections for the 1734-IB8S module have 2 bytes. If you
had selected individual point status, the input connection would be
5 bytes.
11. Click Apply.
For further details, see the SmartGuard 600 Controllers User Manual,
publication 1752-UM001, and SmartGuard 600 Controllers Safety
Reference Manual, publication 1752-RM001.
Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Configure the Module for a SmartGuard Controller
3...9
for each connection, being sure to assign input and
Chapter 7
107